User`s manual

112
Register Number Allocations in Detail Chapter 7-7
Broadcast Message with Slave Address: 00 (00 Hex) Write
Note 1. Data can be written to registers 0001 and 0002 only. Assumed previous
values are held for unused registers.
2. No data can be written to multi-function input.
3. The unit of setting of the broadcast message is different from that in the
DSR message to communicate with a single Slave.
RUN Command (Register 0001 Hex)
7-7-2 Monitor Functions
Register No. (Hex) Function Description
0000 Not used. ---
0001 RUN command Refer to the table below.
0002 Frequency reference Set the frequency reference based on the maximum
frequency as 30,000.
0003 to 000F Not used. ---
Bit No. Function
0 RUN command (1: RUN)
1 Forward/Reverse (1: Reverse)
2 to 3 Not used.
4 External fault (1: External fault EF0)
5 Fault reset (1: Fault reset)
4 to 15 Not used.
Register No. (Hex) Function Description
0020 Status signal Refer to the following corresponding table.
0021 Fault status Refer to the following corresponding table.
0022 Data link status Refer to the following corresponding table.
0023 Frequency reference According to the set value in n69.
0024 Output frequency According to the set value in n69.
0025 to 0026 Not used. ---
0027 Output current Read based on 1 A as 10.
0028 Output voltage Read based on 1 V as 1.
0029 to 002A Not used. ---
002B Input terminal status Refer to the following corresponding table.
002C Inverter status 1 Refer to the following corresponding table.
002D Output terminal status Refer to the following corresponding table.
002E to 0030 Not used. ---
0031 Main circuit DC voltage Read based on 1 V as 1.
0032 to 003C Not used. ---
003D Communications error Refer to the following corresponding table.
003E to 00FF Not used. ---