User`s manual
120
Protective and Diagnostic Functions Chapter 8-1
f00 Digital Operator transmission
fault 1 (F00)
An initial memory fault has been
detected
• The internal circuitry of the Inverter has a fault.
→ Turn the Inverter off and on.
→ Replace the Inverter if the same fault occurs again.
f01 Digital Operator transmission
fault 2 (F01)
A ROM fault has been detected.
• The internal circuitry of the Inverter has a fault.
→ Turn the Inverter off and on.
→ Replace the Inverter if the same fault occurs again.
f04 Initial memory fault (F04)
An error in the built-in EEPROM of
the Inverter has been detected.
• The internal circuitry of the Inverter has a fault.
→ Initialize the Inverter with n01 set to 8 or 9 and turn the Inverter
off and on.
→ Replace the Inverter if the same fault occurs again.
f05 Analog-to-digital converter fault
(F05)
An analog-to-digital converter fault
has been detected.
• The internal circuitry of the Inverter has a fault.
→ Turn the Inverter off and on.
→ Replace the Inverter if the same fault occurs again.
f07 Digital Operator fault (F07)
An error in the built-in control
circuit of the Digital Operator has
been detected.
• The internal circuitry of the Digital Operator has a fault.
→ Turn the Digital Operator off and on.
→ Replace the Digital Operator if the same fault occurs again.
ce Communications time-over (CE)
Normal RS-422A/485
communications were not
established within 2 s.
The Inverter will detect this error
if n68 (RS-422A/485
communications time-over
detection selection) is set to
0, 1, or 2.
• A short-circuit, ground fault, or disconnection has occurred on the
communications line.
→ Check and correct the line.
• The termination resistance setting is incorrect.
→ Set the termination resistance of only the Inverter located at
each end of the network to ON.
• Noise influence.
→ Do not wire the communications line along with power lines
in the same conduit.
→ Use the twisted-pair shielded wire for the communications line,
and ground it at the Master.
• Master’s program error.
→ Check and correct the program so that communications will
be performed more than once every 2-s period.
• Communications circuit damage.
→ If the same error is detected as a result of a self-diagnostic test,
change the Inverter.
stp Emergency stop (STP)
An emergency stop alarm is input
to a multi-function input. (A multi-
function input 1, 2, 3, or 4 set to 19
or 21 has operated.)
• An emergency stop alarm is input to a multi-function input.
→ Remove the cause of the fault.
• The sequence is incorrect.
→ Check and change the external fault input sequence including
the input timing and NO or NC contact.
0ff Power supply error
• Insufficient power supply voltage
• Control power supply fault
• Hardware fault
• No power supply is provided.
→ Check and correct the power supply wire and voltage.
• Terminal screws are loosened.
→ Check and tighten the terminal screws.
• The Inverter is damaged.
→ Replace the Inverter.
Fault
display
Fault name and meaning Probable cause and remedy