Protective and Diagnostic Functions Chapter 8-1
f00 Digital Operator transmission
fault 1 (F00)
An initial memory fault has been
detected
The internal circuitry of the Inverter has a fault.
Turn the Inverter off and on.
Replace the Inverter if the same fault occurs again.
f01 Digital Operator transmission
fault 2 (F01)
A ROM fault has been detected.
The internal circuitry of the Inverter has a fault.
Turn the Inverter off and on.
Replace the Inverter if the same fault occurs again.
f04 Initial memory fault (F04)
An error in the built-in EEPROM of
the Inverter has been detected.
The internal circuitry of the Inverter has a fault.
Initialize the Inverter with n01 set to 8 or 9 and turn the Inverter
off and on.
Replace the Inverter if the same fault occurs again.
f05 Analog-to-digital converter fault
(F05)
An analog-to-digital converter fault
has been detected.
The internal circuitry of the Inverter has a fault.
Turn the Inverter off and on.
Replace the Inverter if the same fault occurs again.
f07 Digital Operator fault (F07)
An error in the built-in control
circuit of the Digital Operator has
been detected.
• The internal circuitry of the Digital Operator has a fault.
Turn the Digital Operator off and on.
Replace the Digital Operator if the same fault occurs again.
ce Communications time-over (CE)
Normal RS-422A/485
communications were not
established within 2 s.
The Inverter will detect this error
if n68 (RS-422A/485
communications time-over
detection selection) is set to
0, 1, or 2.
A short-circuit, ground fault, or disconnection has occurred on the
communications line.
Check and correct the line.
The termination resistance setting is incorrect.
Set the termination resistance of only the Inverter located at
each end of the network to ON.
Noise influence.
Do not wire the communications line along with power lines
in the same conduit.
Use the twisted-pair shielded wire for the communications line,
and ground it at the Master.
Master’s program error.
Check and correct the program so that communications will
be performed more than once every 2-s period.
Communications circuit damage.
If the same error is detected as a result of a self-diagnostic test,
change the Inverter.
stp Emergency stop (STP)
An emergency stop alarm is input
to a multi-function input. (A multi-
function input 1, 2, 3, or 4 set to 19
or 21 has operated.)
An emergency stop alarm is input to a multi-function input.
Remove the cause of the fault.
The sequence is incorrect.
Check and change the external fault input sequence including
the input timing and NO or NC contact.
0ff Power supply error
• Insufficient power supply voltage
• Control power supply fault
• Hardware fault
No power supply is provided.
Check and correct the power supply wire and voltage.
Terminal screws are loosened.
Check and tighten the terminal screws.
The Inverter is damaged.
Replace the Inverter.
Fault
display
Fault name and meaning Probable cause and remedy