User`s manual

132
Inverter Specifications Chapter 9-1
9-1 Inverter Specifications
3-phase
200-V AC
models
Model CIMR-J´7AZ 20P1 20P2 20P4 20P7 21P5 22P2 24P0
Power
supply
Rated voltage
and frequency
3-phase 200 to 230 V AC at 50/60 Hz
Allowable voltage
fluctuation
–15% to 10%
Allowable frequency
fluctuation
±5%
Power supply capacity (kVA)
(See note 1.)
0.4 0.9 1.6 2.7 4.3 5.9 9.3
Heat radiation (W) 13.0 18.0 28.1 45.1 72.8 94.8 149.1
Weight (kg) 0.5 0.5 0.8 0.9 1.3 1.5 2.1
Cooling method Natural cooling Cooling fan
Single-
phase
200-V AC
models
Model CIMR-J7AZ B0P1 B0P2 B0P4 B0P7 B1P5 --- ---
Power
supply
Rated voltage and
frequency
Single-phase 200 to 240 V AC at 50/60 Hz
Allowable voltage
fluctuation
–15% to 10%
Allowable frequency
fluctuation
±5%
Power supply capacity (kVA)
(See note 1.)
0.5 0.9 1.6 2.7 4.3 --- ---
Heat radiation (W)
(See note 2.)
14.1 20.0 31.9 51.4 82.8 --- ---
Weight (kg) 0.5 0.5 0.9 1.5 1.5 --- ---
Cooling method Natural cooling Cooling fan
Max. applicable motor capacity (kW) 0.1 0.2 0.4 0.75 1.5 2.2 3.7
Output
specifi-
cations
Rated output capacity (kVA) 0.3 0.6 1.1 1.9 3.0 4.2 6.7
Rated output current (A) 0.8 1.6 3.0 5.0 8.0 11.0 17.5
Rated output voltage (V) 3-phase 200 to 240 V AC (according to the input voltage)
Max. output frequency 400 Hz parameter setting
Control
charac-
teristics
Harmonic-current
countermeasures
DC reactor (option) connection possible
Control method Sine wave PWM (V/f control)
Carrier frequency 2.5 to 10.0 kHz (in vector control)
Frequency control range 0.1 to 400 Hz
Frequency precision
(temperature characteristics)
Digital commands: ±0.01% (–10°C to 50°C)
Analog commands: ±0.5% (25°C ±10°C)
Frequency setting resolution Digital commands: 0.1 Hz (less than 100 Hz) and 1 Hz (100 Hz or over)
Analog commands: 0.06 Hz/60 Hz (equivalent to 1/1000)
Output frequency resolution 0.01 Hz