152
List of Parameters Chapter 10
n40
(0128)
Multi-function
output
(MA/MB
and MC output
terminals)
Used to select the functions of multi-function
output terminals.
0 to 7,
10 to
17
11No 5-20
Set
value
Function Description
0 Fault output ON: Fault output
(with protective
function working)
1 Operation in
progress
ON: Operation in
progress
2 Frequency
detection ยด
ON: Frequency
detection (with
frequency reference
coinciding with output
frequency)
3 Idling ON: Idling (at less
than min. output
frequency)
4 Frequency
detection 1
ON: Output frequency
P frequency detection
level (n58)
5 Frequency
detection 2
ON: Output frequency
O frequency detection
level (n58)
6 Overtorque
being
monitored
(NO-contact
output)
Output if any of the
following parameter
conditions is satisfied.
n59: Overtorque
detection function
selection
n60: Overtorque
detection level
n61: Overtorque
detection time
NO contact: ON
with overtorque being
detected
NC contact: OFF
with overtorque being
detected
7 Overture
being
monitored
(NC-contact
output)
8 Not used ---
9
10 Alarm output ON: Alarm being
detected
(Nonfatal error being
detected)
11 Base block
in progress
Base block in
progress (in operation
with output shut-off)
12 RUN mode ON: Local mode (with
the Digital Operator)
13 Inverter
ready
ON: Inverter ready to
operate (with no fault
detected)
14 Fault retry ON: Fault retry
15 UV in
progress
ON: Undervoltage
being monitored
Para-
meter No.
(Register
No. (Hex))
Name Description Setting
range
Unit of
setting
Default
setting
Changes
during
operation
Refer-
ence
page