User`s manual

155
List of Parameters Chapter 10
062
(013E)
UP/DOWN
command
frequency
memory
Used to store the adjusted frequency
reference with the UP/DOWN function.
0:Frequency not stored
1:Frequency stored
The frequency must be on hold for 5 s
or more.
Used to store the adjusted frequency
reference with the UP/DOWN function.
0:Frequency not stored
1:Frequency store
The frequency must be on hold for 5 s
or more.
Used to store the adjusted frequency
reference with the UP/DOWN function.
0:Frequency not stored
1:Frequency stored
The frequency must be on hold for 5 s
or more.
0, 1 1 0 No 6-19
n63
(013F)
Torque
compensation
gain
Used to set the gain of the torque
compensation function.
The default setting does not need any
changes in normal operation.
0.0 to
2.5
0.1 1.0 Yes 6-11
n64
(0140)
Motor rated
slip
Used to set the rated slip value of the motor
in use.
Note Used as the constant of the slip
compensation function.
0.0 to
20.0
0.1 Hz Varies
with
the
capac-
ity.
Ye s 6 - 1 2
n65
(0141)
Motor no-load
current
Used to set the no-load current of the motor
in use based on the rated motor current as
100%.
Note Used as the constant of the slip
compensation function.
0 to 99 1% Varies
with
the
capac-
ity.
No 6-12
n66
(0142)
Slip
compensation
gain
Used to set the gain of the slip
compensation function.
Note The slip compensation function is
disabled with n66 set to 0.0.
0.0 to
2.5
0.1 0.0 Yes 6-12
n67
(0143)
Slip
compensation
time constant
Used for the response speed of the slip
compensation function.
Note The default setting does not need any
changes in normal operation
0.0 to
25.5
0.1 s 2.0 No 6-12
n68
(0141)
(See note
3.)
RS-422A/485
communica-
tions timeover
detection
selection
Used to set whether a communications time-
over (CE) is detected if there is an interval of
more than 2 s, and to select the method of
processing the detected communications
time-over.
0:Detects a time-over and fatal error and
coasts to a stop.
1:Detects a time-over and fatal error
and decelerates to a stop in deceleration
time 1.
2:Detects a time-over and fatal error
and decelerates to a stop in deceleration
time 2.
3:Detects a time-over and nonfatal error
warning and continues operating.
4:No time-over is detected.
0 to 4 1 0 No 7-5
Para-
meter No.
(Register
No. (Hex))
Name Description Setting
range
Unit of
setting
Default
setting
Changes
during
operation
Refer-
ence
page