User`s manual
13
Wiring Chapter 2-2
Main Circuit Terminals
Note The maximum output voltage corresponds to the power supply input voltage
of the Inverter.
Symbol Name Description
R/L1 Power Supply input terminals CIMR-J7AZ2_: 3-phase 200 to 230 V AC
CIMR-J7AZB_: Single-phase 200 to 240 V AC
CIMR-J7AZ4_: 3-phase 380 to 460 V AC
Note Connect single-phase input to terminals R/L1 and S/L2.
S/L2
T/L3
U/T1 Motor output terminals 3-phase power supply output for driving motors.
CIMR-J7AZ2_: 3-phase 200 to 230 V AC
CIMR-J7AZB_: 3-phase 200 to 240 V AC
CIMR-J7AZ4_: 3-phase 380 to 460 V AC
V/T2
W/T3
+1 Connection terminals +1 and +2:
DC reactor connection terminals
+1 and –:
DC power supply input terminals
Connect the DC reactor for suppressing harmonics to terminals
+1 and +2.
When driving the Inverter with DC power, input the DC power to
terminals +1 and –.
(Terminal +1 is a positive terminal.)
+2
–
Ground terminal Be sure to ground the terminal under the following conditions.
CIMR-J7AZ2_: Ground at a resistance of 100 Ω or less.
CIMR-J7AZB_: Ground at a resistance of 100 Ω or less.
CIMR-J7AZ4_: Ground at a resistance of 10 Ω or less, and connect
to the power supply’s neutral phase to conform to EC Directives.
Note Be sure to connect the ground terminal directly to the
motor frame ground.