User`s manual

28
Wiring Chapter 2-2
Wiring Method 1. Loosen the terminal screws with a thin-slotted screwdriver.
2. Insert the wires from underneath the terminal block.
3. Tighten each terminal screw firmly to a torque specified in the previous
tables.
Note 1. Always separate the control signal line from the main circuit cables and
other power cables.
2. Do not solder the wires to the control circuit terminals. The wires may not
contact well with the control circuit terminals if the wires are soldered.
3. The end of each wire connected to the control circuit terminals must be
stripped for approximately 5.5 mm.
4. Connect the shield wire to the ground terminal of the CIMR-J7AZ. Do not
connect the shield wire to the device side being controlled.
5. Be sure to insulate the shield wire with tape so that the shield wire will not
come into contact with other signal wires or equipment.
Applying excessive torque may damage
the terminal block. If the tightening torque
is insufficient, homever, wires may dis-
connect.
Note
Thin-slotted screwdriver
Terminal block
Solderless terminal or
wire without soldering.
Wire
Strip the end for approximately
5.5 mm if no solderless
terminal is used.