Outline of Operation Chapter 3-2
Example of Frequency Reference Settings
Note 1. The Enter Key need not be pressed when performing the setting for n08.
The frequency reference will change when the set value is changed with
the Increment or Decrement Key while the data display is continuously lit.
2. The frequency reference can be set in either of the following cases.
Parameter n03 for frequency reference selection is set to 1 (i.e., frequen-
cy reference 1 is enabled) and the Inverter is in remote mode.
• Parameter n07 for frequency selection in local mode is set to 1 (i.e., the
Digital Operator is enabled) and the Inverter is in local mode.
Frequency references 2 through 8 are input for multi-step speed
operation.
3. The frequency reference can be changed, even during operation.
Example of Multi-function Display
Key sequence Indicator Explanation
Display
example
Power ON
Note If the FREF indicator has not been lit, press the
Mode Key repeatedly unit the FREF indicator is lit.
Use the Increment or Decrement Key to set the
frequency reference.
The data display will flash while the frequency
reference is set. (see note 1)
Press the Enter Key so that the set value will be
entered and the data display will be lit. (see note 1)
Key sequence Indicator Display Explanation
Power ON
Press the Mode Key repeatedly until the MNTR
indicator is lit.
U01 will be displayed.
Use the Increment or Decrement Key to select the
monitor item to be displayed.
Press the Enter Key so that the data of the selected
monitor item will be displayed.
The monitor number display will appear again by
pressing the Mode Key.