User`s manual

54
Selecting the Operation Command Chapter 5-4
5-4 Selecting the Operation Command
The following description provides information on how to input operation
commands to start or stop the Inverter or change the direction of rotation of
the Inverter.
Three types of command input methods are available. Select either one of
them according to the application.
Selecting the Operation Mode (n02)
Select the method of operation mode input to start or stop the Inverter.
The following method is enabled in remote mode only. The command can
be input through key sequences on the Digital Operator.
Set Values
Selecting the STOP/RESET Key Function (n06)
When parameter n02 is set to 1, set whether or not to use the STOP/
RESET Key of the Digital Operator to stop the Inverter in remote mode.
The STOP/RESET Key is always enabled in local mode regardless of the
setting in n02.
Set Values
n02 Operation Command Selection Changes during
operation
No
Setting
range
0 to 2 Unit of
setting
1 Default setting 0
Value Description
0 The RUN and STOP/RESET Keys of the Digital Operator are enabled.
1 Multi-function input in 2- or 3-wire sequence through the control circuit terminals is enabled.
2 Operation commands via RS-422A/485 communications are enabled.
n06 STOP Key Function Selection Changes during
operation
No
Setting
range
0, 1 Unit of
setting
1 Default setting 0
Value Description
0 The STOP/RESET Key of the Digital Operator is enabled.
1 The STOP/RESET Key of the Digital Operator is disabled. This setting is available only when the Digital
Operator is selected for operation command input.