Specifications

147
Manufacturer reserves the rights to change specications without prior notice.
Technical features
INDOOR UNITS
Cooling only and Reverse cycle SICH 76 90 120 150 180 240 300
OUTDOOR UNITS
Cooling only models SOC 76 90 120 150 180 240 300
Cooling capacities
kW 22.00 29.00 33.40 41.80 53.00 68.00 85.00
Power input in cooling
kW 7.89 12.20 14.00 17.00 19.40 28.00 33.00
Refrigerant charge on site
for 7 m piping length
kg 6.6 7.8 11.2 6.7 x 2 8.7 x 2 10 x 2 16 x 2
Reverse cycle models SOH 76 90 120 150 180 240 300
Cooling capacities
kW 22.00 29.00 33.40 38.50 54.00 68.00 83.00
Power input in cooling
kW 7.91 11.00 13.80 16.00 20.80 28.00 32.60
Heating capacities
kW 23.00 30.00 34.00 43.00 55.50 67.80 89.00
Power input in heating
kW 6.30 8.65 12.10 15.00 19.40 22.30 30.50
Refrigerant charge on site
for 7 m piping length
kg 8.9 11.4 12.4 9 x 2 10 x 2 13 x 2 15 x 2
Ambient outdoor side sound power
level SOC / SOH
dB(A) 73 / 75 80 / 74 77 / 79 86 / 86 86 / 83 82 / 82 86 / 86
Ambient outdoor side sound pressure
level at 5 m SOC / SOH
dB(A) 51 / 52 57 / 57 55 / 57 63 / 63 64 / 61 60 / 60 62
In duct indoor side sound power level
dB(A) 70 84 84 85 89 77 86
Power supply
400V/3 + N/ 50Hz
Nominal / Starting current
A 17/ 99 23/ 134 28/ 167 31/ 2 x 99 44/ 2 x 134 56/ 2 x 167 61/ 2 x 189
Main switch (1)
A 25 32 40 50 63 80 80
Main cable to the outdoor unit (1)
Nbr x mm
2
5 x 4 5 x 6 5 x 10 5 x 10 5 x 16 5 x 25 5 x 25
Interconnecting cable (1)
Nbr x mm
2
4 x 1,5 4 x 1,5 4 x 1,5 4 x 1,5 4 x 1,5 4 x 1,5 4 x 2,5
Cable to standard thermostat (2)
Nbr x mm
2
10 x 0,22
Insulated refrigerant piping
Suction 1 1/8” 1 1/8” 1 1/8” 2 x 1 1/8” 2 x 1 1/8” 2 x 1 3/8” 2 x 1 3/8”
Liquid 1/2” 5/8” 5/8” 2 x 1/2” 2 x 5/8” 2 x 7/8” 2 x 7/8”
Evaporator fan SICH
at nominal airow (3)
Airow
m
3
/h 4 530 8 500 8 300 10 700 13 600 16 500 19 500
Standard ESP
Pa 62 62 75 75 80 80 80
ESP with HSD
Pa - 138 150 - - - -
ESP with HSDM
Pa 165 - - 112 164 156 187
Nett dimensions
outdoor
Height
mm 1 028 1 180 1 180 1 180 1 230 1 180 1 782
Length
mm 1 245 1 245 1 245 1 245 1 245 1 983 2 454
Depth
mm 885 885 1 632 1 632 1 632 1 635 1 976
Nett dimensions
indoor
Height
mm 590 663 663 663 762 838 838
Length
mm 1 357 1 738 1 738 2 038 2 239 2 639 2 639
Depth
mm 725 725 725 725 777 857 857
Nett weight
SOC
kg 234 234 318 415 430 575 925
SOH
kg 258 268 336 450 495 610 940
SICH
kg 120 165 165 195 240 310 310
(1) For information only. These should be checked for compliance with local regulations depending also on installation and conductor type.
(2) Shield type cable only.
(3) ESP = External static pressure HSD = High speed drive HSDM = High speed drive and motor
All the data are at EUROVENT conditions with 230V/1/50Hz or 400V/3+N/50Hz.
Cooling : Entering indoor coil temp. 27°C / 19°C WB and outdoor temperature 3C
Heating : Entering indoor coil temp. 20°C and outdoor temperature C / 6°C WB
Large Split (Axial)
E-COM-R0804