Specifications

131
Main features
Strategy
Turbo, normal or economy
Auto restart after power failure
l l
Number of cool stages
2 1 2
Number of heat stages
2 1 2
Auxiliary Heat
l l
Automatic Heat/Cool change over
l l
Continuous or auto indoor fan
l l
Manual setback (Day/Night key)
Day, night and unocuppied
Override possibility
l l
Compressor anti short cycle
l l
°C Range cooling / heating
10 to 32°C / 9 to 32°C
Programmable, 7-day
l l
Lockout codes
l l
Outdoor air temperature
l
with YKlon
Sensor selection
l l
X : Delivered as standard with the unit. X (1) : Standard but has to be ordered separately.
O : Optional. l : Function available.
Thermostat models DPC-1 DPC-1R
Code
603786044 603786045
Roomtop RTC and RTH
X 0
Rooftop All models
X (1) 0
Split system
SOC and SOH
X 0
SCOC and SCOH
X 0
Duct sensor Ambiance sensor Room sensor
DS-1 AS-1 * RS-1
603786047 603786049 603786042
* To be tted with DPC-1 version 2.0 or superior
Control System
DS-1
AS-1
RS-1
Led Diagnostic Code
The YKlon is a controller regulating all components and accessories. It will pro actively
manage cool and heat stages to maintain a stable room temperature.
Additionally, the benets are:
• Redundancy on cool and heat stages (if one step is locked out, the PCB
starts another one automatically).
• Random start between units to minimise electrical tariff.
• All stages will start in sequence to reduce peak inrush.
• Reduces nuisance calls by using 3 times “you are out” on all safeties
before a hard lockout occurs.
• Automatic restart after power failure.
• Compressors run time priority.
• Alarm output relay and led diagnostic code.
• No parameters to check before starting.
• Lockout and incident level of protection.
• Use a standard 2-stage thermostat but get 98% of YKlon features.
• Last 10 lockouts stored in a non-volatile memory.
• 4 heating stages on hot water heating.
Features and benets YKtool
• Cooling and defrost test.
• Reverse cycle, gas, hot water and electrical heating test.
• Give access to input and output of the YKlon.
• Give access to accessories status and read the probe values.
LOCKOUT
INCIDENT
Flashes
IncidentType
Probes
Discharge probe open or > 150ºC
Liquid probe open or short circuited
Outdoor probe open or short circuited
Indoor probe open or short circuited
Outdoor temperature too low
Flashes
Meaning
Discharge temperature surpassed or probe short circuited
High pressure switch
Low pressure switch
Indoor or outdoor fan thermal switch
Repeated start-ups in cool, or suction temperature of <-25ºC
Liquid temperature of <-30ºC
LOCKOUT
INCIDENT
Flashes
IncidentType
Probes
Discharge probe open or > 150ºC
Liquid probe open or short circuited
Outdoor probe open or short circuited
Indoor probe open or short circuited
Outdoor temperature too low
Flashes
Meaning
Discharge temperature surpassed or probe short circuited
High pressure switch
Low pressure switch
Indoor or outdoor fan thermal switch
Repeated start-ups in cool, or suction temperature of <-25ºC
Liquid temperature of <-30ºC
Thermostats with integrated sensors
The YKPhone485 is a complete communication pack that YORK can offer in order to
provide a local network between units. Without any specic communication protocol
knowledge, you can download the software and have a direct access to the units,
change thermostat parameters, reset lockout, etc…. For more detail, see the following
pages or contact you local agency.