2. STATUS KEY: GENERAL STATUS MESSAGES & FAULT WARNINGS
2.1 GENERAL
Pressing the Status key displays the current chiller or
individual system operational status. The messages dis-
played include running status, cooling demand, fault
sta tus, external cycling device status, load limiting, and
anti-recycle timer status. The display will show one mes-
sage relating to the “highest priority” information as
de ter mined by the microprocessor.
For individual system status or fault messages, the
dis play shows information for up to two refrigerant
sys tems.
The main categories of messages available using the
Status key are:
2.2 General Status Messages
2.3 Unit Warnings
2.4 Anticipation Control Status Messages
2.5 Chiller Fault Status Messages
2.6 System Fault Status Messages
These messages are described in detail below, with ex-
am ples of each display. In each example “#” is used as
applicable to represent the system number where mes-
sag es apply to individual systems.
2.2 GENERAL STATUS MESSAGES
Unit Switch OFF:
This message indicates that the Chiller ON / OFF Switch
on the Control Panel is in the OFF position which will
not allow the chiller to run.
Schedule Shutdown:
This message indicates that the that the chiller has been
shut down by the daily schedule programmed into the
Clock - Set Schedule / Holiday (Section 7.3).
Compressors Running:
This message indicates that the respective compressor
is running due to demand.
Remote Controlled Shutdown:
This message indicates that either an ISN or RCC (Re-
mote Control Center) has turned the unit OFF through
the RS-485 port.
U N I T S W I T C H O F F
S H U T D O W N
D A I L Y S C H E D U L E
S H U T D O W N
S Y S # C O M P R U N N I N G
S Y S # C O M P R U N N I N G
R E M O T E CO N T RO L L E D
S H U T D O W N
29023A