Fan User Manual

183
YORK INTERNATIONAL
FORM 201.19-NM1 (204)
8
TABLE 7 – YCAS STYLE G, WYE DELTA START - 60 HZ. (CONT'D)
MODEL
NO.
VOLTAGE
CODE
CHILLER
NAMEPLATE
RLA
NO. OF
LEADS
PER PHASE
THRU CT.
100% FLA
OF SYSTEM
MP INPUT
VOLTAGE
200
17 342 *4 369 2.98
28 298 *4 322 2.60
40 181 *2 195 3.15
46 149 2 161 4.47
58 119 2 129 3.58
210
SYS 1
17 374 *4 403 3.24
28 325 *4 351 2.82
40 197 *2 213 3.42
46 163 *2 176 2.84
58 130 2 140 3.89
210
SYS 2
17 342 *4 369 2.98
28 298 *4 322 2.60
40 181 *2 195 3.15
46 149 2 161 4.47
58 119 2 129 3.58
230
17 374 *4 403 3.24
28 325 *4 351 2.82
40 197 *2 213 3.42
46 163 *2 176 2.84
58 130 2 140 3.89
* Indicates one lead/phase through motor protector.