Fan User Manual

200
YORK INTERNATIONAL
FORM 201.19-NM1 (204)
TROUBLESHOOTING GUIDE
Troubleshooting
PROBLEM POSSIBLE CAUSE ACTION POSSIBLE CAUSE ACTION
No display on panel - Main supply to control system OFF. Switch on main supply if safe to do so.
unit will not start
Emergency stop device off.
Check if control panel emergency stop switch
and any remote emergency stop devices are in
the OFF position. Turn to ON position (1) if safe
to do so.
CB3 tripped. Check CB3.
No supply to - T2. Check 115VAC to L & 2.
No 24VAC supply to power board. Check wiring from - T2 to powerboard and fuse.
No +12V output from powerboard.
Replace powerboard or isolate excessive load on
the board.
NO RUN PERM displayed
No liquid ow through the evaporator.
Ensure that liquid pumps are running. Valves are
(No run permissive) correctly set and ow is established.
Flow switch contacts are not made.
Check that the ow switch is functional and is
installed according to the manufacturer’s instructions.
Check cycling contacts.
SYS # HIGH OIL TEMP Poor air ow through the condenser Check for air ow restrictions caused by blockages on
coils. intake faces of air coils.
Measured temperature incorrect. Check oil temp sensor and wiring.
Chiller FAULT: LOW Ambient air temperature is lower Use the ‘ambient temp.’ key to display the
AMBIENT TEMP displayed than the programmed operating temperature and con rm that the displayed value is
limit. approximately correct. The warning message should
clear when the ambient air temperature rises above
the programmed operating limit.
Check the programmed settings are correct for the
options tted to the unit.
Measured temperature is incorrect. Check ambient sensor and wiring.
Chiller FAULT: HIGH Ambient air temperature is higher Use the ‘ambient temp.’ key to display the
AMBIENT TEMP displayed than the programmed operating limit. temperature and con rm that the displayed value is
approximately correct. The warning message should
clear when the ambient air temperature falls below
the programmed operating limit.
Check that the programmed settings are correct for
the options tted to the unit.
Resid. heat is not being dissipated.
Check fans are operating correctly and the rotation is
correct. Check for air ow recirculation.
Measured temperature is incorrect. Check ambient sensor and wiring.
Chiller FAULT: LOW Leaving liquid drops below the Check for restrictions in the liquid ow line.
WATER TEMP displayed programmed low limit faster than the Check that the liquid ow is stable.
unit can unload.
Unit is not unloading.
Check the voltage to the unloader valve solenoid.
Check that the compressor unloads correctly.
Measured temperature is incorrect. Check water temp sensor and wiring.
Chiller FAULT: VAC Check main supply is stable and within allowable
UNDERVOLTAGE Poor main supply voltage. limits.
displayed. Check for voltage dip on compressor start.
Flow switch or cycling contacts are
not made.
Recirculated air is affecting the sensor.