Fan User Manual

50
YORK INTERNATIONAL
FORM 201.19-NM1 (204)
TEMPERATURE AND FLOWS
(SI UNITS)
Technical Data
MODEL
NUMBER
YCAS
LEAVING WATER
TEMPERATURE (°C)
Evaporator FLOW
(l/s
3
)
AIR ON CONDENSER (°C)
MIN.
1
MAX.
2
MIN. MAX. MIN. MAX
0130EC 4.4 12.8 8.7 33.1 -17.7 51.7
0140EC 4.4 12.8 8.7 33.1 -17.7 51.7
0150EC 4.4 12.8 12.6 37.9 -17.7 51.7
0160EC 4.4 12.8 12.6 37.9 -17.7 51.7
0170EC 4.4 12.8 12.6 37.9 -17.7 51.7
0180EC 4.4 12.8 12.6 37.9 -17.7 51.7
0200EC 4.4 12.8 15.8 47.3 -17.7 51.7
0210EC 4.4 12.8 15.8 47.3 -17.7 51.7
0230EC 4.4 12.8 15.8 47.3 -17.7 51.7
Excessive ow, above the max GPM,
will damage the evaporator.
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK of ce for application requirements.
2. For leaving water temperature higher than 55°F (12.8°C), contact the nearest YORK of ce for application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.