Specifications

2=CA""
4.8 SEQUENCE FOR AC INVERTER TRACTION SETTING
When the "Key Switch" is closed, if no alarms or errors are present, the Console Display
will be showing the Standard Zapi Opening Display.
If the chopper is not configured to your requirements, follow the sequence detailed on
Chapter 5.2 . Remember to re-cycle the Key Switch if you make any changes to the
choppers configuration. Otherwise follow the sequence detailed below :
1) Select the Options required. See Chapter 4.1 ÷ 4.4.
2) Select and set the Battery Voltage. See Chapter 4.4.
3) Confirm correct installation of all wires. Use the Consoles TESTER function to
assist.
4) Perform the accelerator signal acquisition procedure using the Console PRO-
GRAM VACC. Procedure is detailed on Chapter 5.4.
5) Set the "MAXIMUM CURRENT Current, using the table on Chapter 4.5 , 4.6.
6) Set the Acceleration Delay requirements for the machine. Test the parameters in
both directions.
7) Set the FREQUENCY CREEP level starting from level 0.6 Hz. The machine should
just move when the accelerator microswitch is closed. Increase the Level accord-
ingly.
8) Set the Speed Reductions as required. Make adjustments to CUTBACK SPEED
Check the performance with the accelerator pedal totally depressed. If the machine
is a forklift, check the performance with and without load.
9) RELEASE BRAKING. Operate the machine at full speed. Release the accelerator
pedal. Adjust the level to your requirements. If the machine is a forklift, check the
performance with and without load.
10) INVERSION BRAKING. Operate the machine at 25% full speed. Whilst traveling
INVERT the Direction Switch. Set a soft Level of Inversion Braking. When satisfac-
tory, operate the machine at Full Speed and repeat. If the machine is a Forklift, re-
peat the tests and make adjustments with and without load. The unladen full speed
condition should be the most representative condition.
11) PEDAL BRAKING (If used). Operate the machine at full Speed. Release the accel-
erator pedal and press the Pedal Brake. Set braking level to your requirements.
12) Set MAX SPEED FORW.
13) Set MAX SPEED BACK (Reverse).
14) Make the choice for the truck behaviour on a slope (see chapter 4.4). If the "Stop on
ramp" option is ON, set the desired value of "auxiliary time" parameter.