Installation Guide

Model 375, 375B
Reduced Pressure Principle (1-1/4"-2")
375 REDUCED PRESSURE PRINCIPLE
1. Start with both shut-off valves closed.
Slowly open the inlet shut-off valve until the
backow preventer is completely pressur-
ized. A brief discharge from the relief valve
may occur while the device is pressurizing.
The discharge should cease by the time the
shut-off valve is fully open. Device should
function properly. If the discharge does not
stop, refer to "MAINTENANCE INSTRUC-
TIONS" for repair procedures.
2. After the device has been pressurized,
vent all trapped air from both check valves
by slightly opening each of the four test
cocks.
3. Slowly open the downstream shut-off
valve. The Model 375 Reduced Pressure
Principle Backow Preventer is now in
service.
4. If "spitting" or intermittent discharges
from the relief valve are noted, it could be a
result of pressure uctuation and/or a water
hammer condition in the system. If such
conditions exist, install a ZURN WILKINS
water pressure reducing valve, a Model
40XL2 check valve, or a Model 1250XL
water hammer shock arrester in compli-
ance with industry standards as needed.
5. After the Model 375 has been prop-
erly installed, test the device (see "TEST
PROCEDURES"). If the device fails the
test, remove the rst and second check
valves and thoroughly ush the device. If
the relief valve fails to operate properly,
inspect the sensing passage for clogging
(see "MAINTENANCE INSTRUCTIONS").
Clean rubber seals of all debris and place
unit back in service.
Installation Testing Maintenance Instructions
FLOOR
DRAIN
INLET SHUT OFF
DIRECTION OF FLOW
12" MIN.
30” MAX.
AIR GAP
OPTIONAL
WATER
METER
175 PSIG 180° F
3/4" 375 RP
ZURN
WILKINS
2” PIPE
(DRAIN LINE CAN
BE ANY STANDARD
PIPING MATERIAL)
PROTECTIVE
ENCLOSURE
4. Install valve at least 12 inches above
surrounding ood level.
5. Always consult local codes for installa-
tion methods, approvals and guidance.
OUTDOOR INSTALLATION
Model 375 Backow Preventers may be
installed outdoors only if the device is
protected against freezing conditions.
Exposure to freezing conditions will result
in improper function or damage to the
device. The installation location must be
kept above 32°F. All the basic installation
instructions apply.
If installation is in a pit or vault, the Back-
ow Preventer must never be submerged
in water because this will cause a cross-
connection. Make sure that the pit or vault
always remains dry by providing ample
drainage.
INDOOR INSTALLATION
Indoor installation is preferred in areas
that are subject to freezing conditions. All
the basic installation instructions apply to
such installations.
PARALLEL INSTALLATION
Where uninterrupted service from a single
meter connection must be maintained, two
or more Backow Preventers may be con-
nected in parallel. All the basic installation
instructions apply to parallel installation.
Be sure to allow adequate room between
the units for testing and repair.
PLACING THE DEVICE IN SERVICE
After the installation of a Model 375 has
been completed, place the unit in service
as follows:
Proposition 65 Warning This product contains chemicals known to the State of California to cause cancer
or birth defects or other reproductive harm.
CAUTION: Installation of Backow Pre-
venters must be performed by qualied,
licensed personnel. The installer should
be sure the proper device has been
selected for the particular installation.
Faulty installation could result in an
improperly functioning device.
ZURN WILKINS Model 375 Reduced
Pressure Principle Backow Preventers
are for use on water lines where a health
hazard could exist if a backow situation
were to occur.
Proper performance is dependent upon
following these installation instructions and
prevailing governmental and industry stan-
dards and codes. Failure to do so, according
to ZURN WILKINS Limited Warranty "...
releases ZURN WILKINS of any liability
that it might otherwise have with respect to
that device." Such failure could also result
in an improperly functioning device.
Damage to the device could result wherever
water hammer and/or water thermal expan-
sion could create excessive line pressure.
Where this could occur, shock arresters
and/or pressure relief valves should be
installed downstream of the device.
1. Before installing a Model 375 Backow
Preventer, ush the line thoroughly to remove
all debris, chips and other foreign matter. If re-
quired, a strainer should be placed upstream
of the Backow Preventer.
CAUTION: Do not use a strainer in sel-
dom used emergency waterlines such
as re lines.
2. Provide adequate space around the
installed unit so that the test cocks will be
accessible for testing and servicing.
3. WARNING: If installation of a Model
375 is in a building, a suitable drain ar-
rangement MUST be provided to drain
off spillage from the relief valve. An air
gap at least two times the pipe diameter
must be provided between the relief valve
and the drain piping to prevent a cross-
connection. Air Gap AG-12 not intended
to support weight of drain pipe.
CAUTION: Do not pipe the relief valve
solidly to a oor drain, sewer or sump.
CAUTION: An adequately sized drain is
required to prevent possible water dam-
age due to relief valve discharge.
®
In accordance with U.S. Federal Safe Drinking Water Act Lead-Free requirements, as of January 4, 2014, this product can only be used in water
systems considered non-potable. Please contact your local water utility for further requirements.