Specification
ഌ
. / 0 1 2 3 4 5 6 7 1 8 0 / 9 4 : 8 ; 1 2 9 < / = = > 5 ? / 4 / @ 1 A B : 1 8 C
Flow Characteristics
Zurn Industries, LLC
| Wilkins
1747 Commerce Way, Paso Robles, CA U.S.A. 93446 Ph. 855-663-9876, Fax 805-238-5766
In Canada | Zurn Industries Limited
3544 Nashua Drive, Mississauga, Ontario L4V 1L2 Ph. 905-405-8272, Fax 905-405-1292
www.zurn.com
Page 2 of 2
DIRECTION OF FLOW
12" MIN.
30" MAX.
OPTIONAL PRESSURE
GAUGE
MODEL 975XL2
BACKFLOW PREVENTER
PROTECTIVE
ENCLOSURE
WILKINS
600XL
WILKINS
ZURN
975XL2
ASSE 1013
Speci cations
The Pressure Reducing Valve shall be certified to NSF/ANSI 372, consist of a low lead bronze body and bronze bell housing,
shall have separate access covers for the plunger and strainer screen and shall have a bolt to adjust the downstream pres-
sure. The Pressure Reducing Valve shall be of the balanced piston design and shall reduce pressure in both flow and no-flow
conditions. The bronze bell housing and access caps shall be threaded to the body and shall not require the use of ferrous
screws. The Pressure Reducing Valve shall be a ZURN WILKINS Model 600XL.
Typical Installation
Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted in accor-
dance with the latest edition of the Uniform Plumbing Code. The Model 600XL may be installed in any position. If installed in
a pit, vault or inside application, specify the “SC” sealed cage option. Multiple installations are recommend for wide demand
variations or where the desired pressure reduction is more than 4 to 1 (i.e.: 200 psi inlet reduced to 50 psi outlet). CAUTION:
Anytime a reducing valve is adjusted, a pressure gauge must be used downstream to verify correct pressure setting. Do not
bottom adjustment bolt on bell housing.
OUTDOOR INSTALLATION VERTICAL INSTALLATION
DIRECTION OF FLOW
MODEL 850XL
SHUT-OFF
600XL
WILKINS
OPTIONAL
PRESSURE GAUGE
FLOW RATES (GPM)
FALL OFF (PSIG)
0
5
10
15
0 40 80
120
69
104
2.5 5.0
7.6
FALL OFF (kpa)
FLOW RATES (l/s)
MODEL 600XL 1/2" THRU 2" (STANDARD & METRIC)
3/4"
(20mm)
35
20
138
1/2"
(15mm)
1"
(25mm)
1 1/4"
(32mm)
1 1/2"
(40mm)
2"
(50mm)
20
60
100
1.3
3.8
6.3
"Flow curves are based on a
50 psi pressure differential"