Eltako Current limiting relay capacitive 230V/240 microfarad. 1 NO 16A/250V AC Blue

22100430

Categories

Description

Current limiting relay with 1 NO contact 16A/250VAC. No standby loss. 1 division unit. Maximum capacitive load 240 microfarad after rectifier (e.g. energy-saving lamps and ECGs) or 120 microfarad directly on the mains (e.g. parallel compensated fluorescent lamps). Limiting resistance 12 Ohm, limiting duration approx. 15ms. The inrush current pulse of energy-saving lamps, fluorescent lamps and compact fluorescent lamps is limited to 20A by short-term (approx. 15ms) switching on of high-load resistors (12 Ohm). The current limiting relay is connected downstream of the relay contact to be protected of a switching device. Continuous load max. 1200W, maximum switching frequency 600/h. Explanation of capacitive load specification: The specification of the maximum capacitive load directly on the mains must be taken into account, e.g. for parallel compensated fluorescent lamps or conventional ballasts. In this case, the capacitor parallel to the mains decides on the correct dimensioning for each bulb. The specific...

Manuals

#TitleLanguagesPagesUpdated
1DatasheetDE22024-01-04