Wire to the SDI control panel 2.2
1 | Overview
3.4 | Wire to the SDI control panel
Callout ― Description
1 ― Bosch control panel (GV3 shown)
2 ― Terminal wiring
3 ― B901 Access Control Module
4 ― Interconnect cable (P/N: F01U79745) (included)
Figure 3.3: SDI wiring from control panel to B901
2.2 | Valid addresses for SDI
Valid B901 addresses are dependant on the number of modules allowed 
and the desired failure mode (Fail Safe, Fail Secure) by a particular 
control panel. 
SDI2
RESETZONEX
TAMPER
SDI2
PWR+/R
A/Y
B/G
COM/B
PWR+/R
A/Y
B/G
COM/B
24
25
26
27
28
29
23
26
WARNING!
Multi-Battery 
installation requires
Dual Battery rnes
I r
ir r
Ba
ttery R
er t year t
one or t
tterie
Battery R
er t year t
one or t
tterie
Battery R
er t year t
one or t
tterie
3
2
SDI2
RESETZONEX
TAMPER
SDI2
PWR+/R
A/Y
B/G
COM/B
PWR+/R
A/Y
B/G
COM/B
24
25
26
27
28
29
23
26
WARNING!
Multi-Battery 
installation requires
Dual Battery rnes  
I r
ir r
Ba
ttery R
er t year t
one or t
tterie
Battery R
er t year t
one or t
tterie
Battery R
er t year t
one or t  
tterie
3
4
1
1
B
G
Y
R
Callout ― Description
1 ― Bosch control panel (B9512G shown)
2 ― Terminal wiring
3 ― B901 Access Control Module
4 ― Interconnect cable (P/N: F01U79745) (included)
Figure 3.2: SDI2 wiring from control panel to B901
R
Y
G
B
R
Y
G
B
R
Y
G
B
Commercial Protected-Premises Control Panel
D9412GV3 Control Panel is UL Listed For 
Central Station, Remote Station, Local, 
Auxiliary, 
Proprietary, and Household Fire Alarm, and 
 VOLTAGE RANGES
Open 3.7 - 5.0 VDC Short 0.0 - 1.3 VDC
Normal 2.0 - 3.0 VDC
Reset Pin
Disable all except Battery
Charging and Programming
PERIPHERAL DEVICE CONNECTIONS
RED
POWER +
YELLOW
DATA BUS A
GREEN
DATA BUS B
BLACK
COMMON
ZONEX OUT 1
ZONEX IN 1
NFPA
Style 4.0
Signaling
Line
Circuits
D9412GV3
26
25
ZONEX POWER +
24
ZONEX COMMON
23
SDI Connector
ZONEX OUT 2
ZONEX IN 2
Battery: Replace every 3 to
5 years with one or two Model 
D126 or D1218 12 V Lead Acid 
Batteries.
 Operation Monitor LED
 Pulses when Normal
 Flickers when Ringing
GREEN
Point 8, S3 Option
25
Point 4
16
Point 5
Point 6
17 19
Point 7
Point 8
21
20
22
Minimum system reuirements or Classiication in accordance with 
ANSISIA CP-01-2007:
UL Listed and Classiied control unit Model D9412GV3, D7412GV3, or 
D7212GV3
UL Listed and Classiied keypad Model D1256, D1257, D1260, D1255, 
D1255R, or D1255RW
WARNING
To prevent risk o 
electric shock, 
disconnect AC 
power and 
telephone lines 
beore servicing. 
1815
Not suitable or remote station protected premises 
services where separate transmission circuits
Commercial Protected-Premises Control Panel
D9412GV3 Control Panel is UL Listed For 
Central Station, Remote Station, Local, 
Auxiliary, 
Proprietary, and Household Fire Alarm, and 
 VOLTAGE RANGES
Open 3.7 - 5.0 VDC Short 0.0 - 1.3 VDC
Normal 2.0 - 3.0 VDC
Reset Pin
Disable all except Battery
Charging and Programming
PERIPHERAL DEVICE CONNECTIONS
RED
POWER +
YELLOW
DATA BUS A
GREEN
DATA BUS B
BLACK
COMMON
ZONEX OUT 1
ZONEX IN 1
NFPA
Style 4.0
Signaling
Line
Circuits
D9412GV3
26
25
ZONEX POWER +
24
ZONEX COMMON
23
SDI Connector
ZONEX OUT 2
ZONEX IN 2
Battery: Replace every 3 to
5 years with one or two Model 
D126 or D1218 12 V Lead Acid 
Batteries.
 Operation Monitor LED
 Pulses when Normal
 Flickers when Ringing
GREEN
Point 8, S3 Option
25
Point 4
16
Point 5
Point 6
17 19
Point 7
Point 8
21
20
22
Minimum system reuirements or Classiication in accordance with 
ANSISIA CP-01-2007:
UL Listed and Classiied control unit Model D9412GV3, D7412GV3, or 
D7212GV3
UL Listed and Classiied keypad Model D1256, D1257, D1260, D1255, 
D1255R, or D1255RW
WARNING
To prevent risk o 
electric shock, 
disconnect AC 
power and 
telephone lines 
beore servicing. 
1815
Not suitable or remote station protected premises 
services where separate transmission circuits
1
1
3
3
2
4
3 | Installation
After you set the address switch for the proper address, install the 
module in the enclosure, and then wire it to the control panel.
CAUTION!
Remove all power (AC and battery) before making any 
connections. Failure to do so might result in personal 
injury and/or equipment damage.
3.1 | Mount the module in the enclosure
Mount the module into the enclosure’s 3-hole mounting pattern using 
the supplied mounting screws and mounting bracket. 
Refer to Figure 3.1.
Figure 3.1: Mounting the module in the enclosure
Callout ― Description
1 ― Module with mounting bracket installed
2 ― Enclosure
3 ― Mounting screws (3)
4
2
PWR A  B COM
B
3
1
B
RELAY C
EARTH GROUND
COMMON
10
9
8
7
WARNING! 
Multi-Battery 
installation requires
Model D122 or D122L 
Dual Battery Harness. 
Improper installation 
can be a fire hazard
.
W
equipment. 
any output must be 
supervised.
The syst
contr
DAC, OT, N
This eq
Alar
W
servicing.
OUTPUT
B (2)
OUTPUT
C (3)
R
Callout ― Description
1 ― Control panel COM terminal (B9512G shown)
2 ― 12 VDC regulated power-limited power supply (B520 shown)
3 ― Terminal wiring (PWR and COM terminal wiring)
4 ― B901 Access Control Module
Figure 3.5: Wiring the card reader to the B901
3.6 | Wire to 12VDC power supply (optional)
Refer to Figure 3.5 to wire additional power to a regulated power-
limited power supply for fire protective signaling units and commercial/
residential burglar units.
Control panel Valid B901 
addresses
Designation
B9512G/B9512G-E/
B8512G/B8512G-E
D9412GV4/D7412GV4
D9412GV3/D7412GV3
D9412GV2/D7412GV2,
D9000
81 - 88 Devices 1 - 8
Fail Safe mode = 
door unlocked
91-98 Devices 1 - 8 Fail Se-
cure = door locked
3.5 | Wire to the card reader
Use the terminals labeled LED, DATA1, DATA0, 5.2V or 12V, COM, and T+ 
when wiring the module to a card reader. Refer to Figure 3.4.
3.2 | Mount the access card reader
Refer to your access card reader installation instructions for proper 
installation and maintenance procedures related to your supported 
card reader.
2.1 | Valid addresses for SDI2
Valid B901 addresses are dependant on the number of modules allowed 
by a particular control panel. 
Control panel Valid B901 
addresses
Designation
B9512G/B9512G-E 01 - 32 Devices 1 - 32
B8512G/B8512G-E 01 - 08 Devices 1 - 8
3.3 | Wire to the SDI2 control panel
When you wire the module to a control panel, use the control panel 
terminals labeled R, Y, G, B (PWR, A, B, COM). Connect them to the 
module terminals labeled R, Y, G, B (PWR, A, B, COM). Use either 
terminal strip wiring or interconnect wiring connector to the control 
panel. Do not use both. Refer to Figures 3.2 - 3.3.
W
Br
G
B
P
 T+ COM ZN+ RTE
COM REX 12V 5.2V
2
1
3
DATA DATA BUZZ LED
 0 1
R
Callout ― Description
1 ― Card reader (ARD-AYK12 shown)
2 ― Terminal wiring
3 ― B901 Access Control Module
Figure 3.4: Wiring the card reader to the B901
DOOR
NC C N0
PWR A B COM
1
5
2
3
DOOR
NC C N0
PWR A B COM
1
5
2
4
3
Callout ― Description
1 ― Door
2 ― B901 door lock relay terminal
3 ― B901 terminal
4 ― AUX PWR terminal (12 VDC) (B520 shown)
5 ― Door strike (12 VDC)
Figure 3.6: Wiring the door strike to the B901
Compatible Credential Formats
37-bit HID H10302 (No Site Code)
26-bit HID H10301
EM EM4200 (5-byte or 3-byte)
Control panel Valid B901 
addresses
Designation
B6512 01 - 04 Devices 1 - 4
2 | Address settings
Two address switches determine the address for the B901 
Access Control Module. The control panel uses the address for 
communications. The address also determines the output numbers. Use 
a slotted screwdriver to set the two address switches.
NOTICE!
The module reads the address switch setting only during 
power up. If you change the switches after you apply power to 
the module, you must cycle the power to the module in order 
for the new setting to be enabled.
Set the address switches per the control panel configuration. If 
multiple B901 modules reside on the same system, each B901 module 
must have a unique address. Figure 2.1 shows the address switch 
settings for address 01.
Figure 2.1: Address switches
NOTICE!
Use only Access Control listed power supplies for powering 
door strikes.
NOTICE!
B901 tamper generates an SDI - “Missing Door” or an 
SDI2 - “Module Tamper” message (if Enclosure Tamper 
parameter is set to Yes).
3.7 | Wire to the door strike
A relay provides a dry contact single pull double throw output. Some 
strikes require a closed circuit to unlock the door, while others require 
an open circuit to unlock the door.
• Common (C). For 12/24 VDC strikes, provide input power here 
from the power supply. Refer to Figure 3.6.
• Normally closed (NC). For door strikes that require an interruption 
of power to open. Connect the positive side of the door strike to 
the NC terminal. Refer to Figure 3.6.
• Normally open (NO). For door strikes that require power to open. 
Connect the positive side of the door strike to the NO terminal. 
Refer to Figure 3.6.
The B901 Access Control module is a fully supervised SDI2/SDI 
device that allows access control integration for compatible control 
panels. Each module can store up to 2000 user tokens (on SDI2), 
each with a different access level for each door. Authority for access 
is controlled by the user’s authority level, the time of day, the state 
of the door, and the armed state to the module. 
READER
T+ COM ZN+ RTE COM REX 12V 5.2V DATA0 DATA1 BUZZER LEDNC C N0
PWR A B COM
2
3
4
5
RELAY
1
6
7
8
Figure 1.1: Access control module
Callout ― Description
1 ― Terminal connector
2 ― Interconnect wiring connectors
3 ― Address switch
4 ― Reader LED
5 ― Heartbeat LED (blue)
6 ― Reader and door terminals
7 ― Relay terminals
8 ― Relay LED