Technical Manual

9
1. Direct lock connection
Use the power of the system to supply for the electronic lock, so that the lock can connect to the Door Station directly,
without a additional power supply for the electronic lock. Note that the Door Station can only output a 12Vdc power,
therefore the kind of lock used is limited.
The rated power of the lock must be less than 12Vdc 300mA when using direct lock connection method.
The GND must connect to the negative of the lock, and the COM connect to the positive .
Jumper set to 12 position for PowertoUnlock safety type; set to 23 position for Poweroffto Unlock type(in
this case the Unlock Relay mode should be set to Normally Closed on DT CONFIG software)
The 5th bit of the DIP switches is for the unlocking time setting, it's set to off by default, for 1 second unloking
time. If set this bit to on, the unlocking time is 5 seconds.
If different unlocking time is needed to be congured, the DT CONFIG software can be used to change the
Unlock Timing on the Parameter tab(see the program section).
1 2 3 4 5 6
ON
DIPS
JP_LK
12V 300mA
DIPS-5: default set to off,
unlocking time is 1 second.
(In most cases, 1 second is
work for Power-to-Unlock type)
Jumper set to 1-2 position
+
-
+12V
LK - (GND)
LK+(COM)
N.O.
EB+
EB -
1
2
3
A. Connection for PowertoUnlock type:
Door Station Lock Connections
1 2 3 4 5 6
ON
L1
+12V
T/R -
T/R+
LK - (GND)
CN-LK JP-LK
RS-485
SET
PA
PB
BUS
LK+(COM)
N.O.
EB+
EB -
1
2
3
L2
1 2 3 4 5 6
ON
L1
+12V
T/R -
T/R+
LK - (GND)
CN-LK
RS-485
SET
PA
PB
BUS
LK+(COM)
N.O.
EB+
EB -
1
2
3
L2
DMR11
Connection Board