Manual

2GIGSMKT3345
WIRELESS SMOKE/HEAT/FREEZE ALARM
INSTALL INSTRUCTIONS
FCCID:ZFHSMKT3345
IndustryCanadaID:9640ASMKT3345
2GIG’sWirelessSmoke/Heat/FreezeAlarmisa3xAAAbatterypoweredwirelessalarmintended
foruseina2GIGsystem.Thealarmhasabuiltinwirelesstransmitter,whichcommunicates
withthe2GIGControlPanel.Whensmoke,excessiveheatorcoldisdetected,thealarmsounds
aloudlocalalarmandthebuiltint
ransmittersendsasignaltotheControlPanel.Thisalarmis
designedtoprovideprotectionwithina35footradiusoftheunit.The2GIGSMTK3345can
sendalarm,tamperandbatteryconditionmessagestotheControlPanel.
Box Contents
•WirelessSmoke/HeatAlarm
•Packofscrewsandfixings
•3AAAEnergizerE92batteries(1.5V1100mAh)orequivalent
TheWirelessSmoke/HeatAlarmcontainsasounderthatgeneratestheASHIs3.41temporal3
patterninanalarmcondition.
Inalarm,amessageisalsosenttotheControlPanelandthealarm’szonetypeandnamear
e
displayedatthepanel.Duringanalarmcondition,pressingthealarm’shushbuttonsilencesthe
sounder.TricoloredLED(red,yellow,green)andasounderonthealarmprovidelocalvisualand
audibleindicationofthealarm’sstatus.
Afterpoweruphascompletedandthealarmisfunctioningnormally,thegreenLEDblink
severy12
seconds.
AlarmTrouble:Whenthealarmhasageneralfault,theyellowLEDblinksonceeveryfourseconds
andthereisachirpevery48seconds.After4hoursthe2GIGControlPaneldisplaysalossof
supervisionmessage.
AlarmDirtyFeature:Whenthealarmhasbeencontaminated,they
ellowLEDblinksonceevery8
secondsandthereisachirpevery48seconds.After4hoursthe2GIGControlPaneldisplaysaloss
ofsupervisionmessage.
LowBatteryDetection:TheWirelessSmoke/HeatAlarmispoweredby3AAAbatteries.Thealarm
regularlychecksforalowbattery.Ifalo
wbatteryisdetected,thetransmittersendsalowbattery
messagetothe2GIGControlPanel,thatdisplaysthealarm’sIDatlowbattery.Inaddition,the
yellowLEDofthealarmblinksevery12seconds.Thealarmssounderchirpsevery48seconds
(yellowLEDcontinuestoblink)untiltheba
tteriesarereplaced.Pressingthehushbuttonsilences
thechirpingfor12hoursifnoothertroubleconditionsexist.Replacethebatterieswhenthe
chirpingbegins.Replacetheoldbatterieswithnewones.
Ifyouareexperiencinglowbatteryissues,checktomakesurethatyouhavethecorrectbatteries
installed(3AA
AEnergizerE92).
Inserting and Replacing Batteries
1. Removethealarmfr omitsbasebytwistingtheitcounterclockwise.Removeanddisposeof
thebatteriesaccordingtoyourlocalregulations.
2. Toensureproperpowerdownsequence,waitaminimumof20secondsbefore
insertingnewbatteries.
3. Insert3AAAEnergizerE92batteriesinthebatterycompartment.Followthepolaritydiagr
am
insidethecompartment.Ifthebatteriesareinsertedincorrectly,removegentlywithanon
conductivetoolandcorrectlyreinsert.
4. Reinstallthealarmontothemountingbasebyturningthealarmclockwiseuntilthemating
marksalign.
5. Afterthepowerupsequence,thegreenLEDshouldblinkaboutonceevery12secondsto
indic
atenormaloperation.Ifthebatteriesarenotinsertedcorrectly,thealarmwillnotoperate
andthebatteriesmaybedamaged.Ifthealarmdoesnotpowerup,checkforcorrectbattery
insertionandforfullychargedbatteries.
Constantexposuretohighhumiditymayreducebatterylife.
Programming
Thefollowingstepsdescribegeneralguidelinesforprogramming(learning)theWireless
Smoke/HeatAlarm(2GIGSMKT3345)intothe2GIGControlPanel.Scrollbetweenoptions
usingthe←and→arrows.Movetothepreviousornextpromptbypressingthe↑and↓
arrows.FormoredetailsregardinghowtoprogramtheControlPanel,refertothe2G
IG
ControlPanelInstallGuide.
1. SelectRFsensor#(01to48).AssigntheWirelessSmoke/HeatAlarmtoanewzone.
2. SelectRFsensortype.
(09)24hourfire(recommendedforsmokeandfire)
(16)24hourfirewithverification(optional)
(23)noresponsetype(optionalwithfreeze)
3. SelectRFequipmenttype.
4. SelectRFsensorequipmentcode.Enter1058forth
eSMKT33452GIG Smoke/HeatAlarm.
5. EnterRFsensorserialnumber(7digits).
ManualEntry:Typeinthelast7digitsoftheTXIDthatisfoundoutsidetheboxoronthe
bottomoftheheadunitbyremovingthebase.
AutoEntry:WiththepanelinLearninmode(p
ressShiftthenLearn)causeatamperonthe
alarmbytwistingthebaseunitcounterclockwiseandremovingit.ThecorrectTXIDshould
appear.A cceptthecorrectTXIDbypressingok.
Remembertopressthe↓arrowtocontinuethroughthesystemconfigurationprompts.
6. SelectRFsensorequipmentage.
(0)new(p
roductisnew)
(1)existing(productalreadyexists).
7. SelectRFsensorloopnumber.Selectwhichloopyouwouldliketosetup.
(1)Smoke
(2)Heat
(3)Freeze
NOTE:Eachloopmustbesetupasadifferentzone.Ifyouwanttoutilizeallthreefeatures
(smoke,heat,freeze)youwillneedtose
tupthreedifferentzonesanduseeachloop.
8. SelectRFsensor1dialerdelay
(0)disabled(thereshouldneverbeadialerdelayonthistypeofalarm)
9. ConstructRFsensordescriptor.PressInsertthenpressanynumberbetween002and255to
addaword.Forexample,ifyouwantedtona
methisalarmas“smokealarm,pressInsertthen
press208forSMOKE.PressInsertthenpress005forALARM.
10. SelectRFsensorreports(0to1).
(0)disabled(sensordoesnotreporttocentralstation)
(1)enabled(sensorreportstothecentralstation)
11. SelectRFsensorsupervised(0to1)
.
(0)disabled(sensordoesnotreportlossofsupervisionorlowbattery)
(1)enabled(sensorreportslossofsupervisionorlowbattery)
12. SelectRFsensorchime(0to13).
(0)disabled(panelwillnotchimewhensensorisactivated)
(1)(13)(selectsavoiceandchimetosoundwhensensorisactivated)
13.
Toprogramanothersensor,clicknext.
14. Toexitprogramming,clickskipthenendandexit.Uponexit,thepaneltakesafewsecondsto
reset.
Testing
Beforete sting,putthepanelintotestmodesothecentralstationisnotnotifiedtoprevent
unwantedalarms.TestingthealarmactivatesanalarmsoundandsendsasignaltotheControl
Panel.Thetestfunctioncannotbeusedifthealarmhasatroublecondition.
Test alarmsounder,LEDsandtransmitter
1.HoldtheTestbuttonfor4beeps(approximately6seconds).
2.ReleasetheTestbutton.
3.Oncereleased,theproductwillcontinuetobeep5moretimes.Bef orethebeepsstop,a
signalwillbesenttriggeringthealarm.
SmokeTest
Holdacottonwickatthesideofthealarmandgentlyblowsmokethroughthealarmuntilthe
smoketriggersthealarm.Youcanalsousesmokeaerosol.
DirectHeatTest (UseHairDryer10001500Watts)
Directheattowardthealarm.Holdtheheatsourceabout12inchesfromthealarmtoavoid
damagetotheplastic.Thealarmresetsonlyafterithastimetocool.
Ifanalarmfailsanyofthesetests,seeMaintenanceforhowtocleanthealarm.
Mounting the Alarm
1. Seethediagramtoinstallthemountingbaseontheceilingoronthewall.Usethe2screwsand
anchorsprovided.Maneuverthebasesothescrewsareattheelbowofthescrewslotsand
secure.
2. F itthe alarminsidethebasebyaligningitoverthebaseasshown(a
larm’salignmentnotch
shouldbeslightlyoffsetfromthemountingbasetamperreleasetab),thenturnthealarm
clockwiseuntilthealarmclicksintothebase.

Summary of content (2 pages)