Cut Sheet
3M™ Cold Shrink QS-III Inline Splice Kits 15 kV 
5415A, 5416A, 5417A, 5417A-WG, 5418A and 5418A-WG 
      3 of 9     78-8125-9882-5 Rev C 
Splice Selection Table 
Kit Number 
Cable Insulation O.D. Range 
Inches (mm) 
Conductor Size Range 
AWG or kcmil (mm
2
) 
5415A  0.64 - 1.01 (16,3 - 25,7)  2 - 4/0 (35 - 95) 
5416A  0.84 - 1.38 (21,3 - 35,1)  4/0 - 350 (95 - 185) 
5417A, 5417A-WG  1.04 - 1.70 (26,4 - 43,2)  350 - 750 (185 - 325) 
5418A, 5418A-WG  1.08 - 1.70 (27,4 - 43,2)  500 - 1000 (240 - 500) 
Table 1 
Typical Dimensions (Installed Splice) 
  On CN Cable       On JCN Cable With Neutral Pad 
Kit Number 
Typical Length (L) 
Inches (mm) 
Typical Diameter (D
1
) 
Inches (mm) 
Typical Diameter (D
2
) 
Inches (mm) 
5415A  28 (711)  2.25 (57)  2.50 (64) 
5416A  29 (736)  2.50 (64)  2.75 (70) 
5417A, 5417A-WG  32 (813)  3.00 (76)  3.25 (83) 
5418A, 5418A-WG  32 (813)  3.00 (76)  3.25 (83) 
Table 3 
Connector Dimensional Requirements Table 
Kit Number 
Minimum 
O.D. 
Inches (mm) 
Maximum 
O.D. 
Inches (mm) 
Maximum Length 
 Inches (mm) 
Connector O.D. 
Range Requiring 
adapters 
Inches (mm) 
Aluminum 
(AI/Cu) 
Compression 
Copper (Cu) 
Compression 
3M™ Shearbolt 
Connector QCI 
Series 
5415A  0.40 (10,2)  1.06 (26,9)  4.50 (114)  5.00 (127)  4.41 (112) 
0.40 - 0.64 
(10,2 - 16,3) 
5416A  0.69 (17,5)  1.38 (35,1)  5.00 (127)  5.75 (146)  5.75 (146) 
0.69 - 0.84 
(17,5 - 21,3) 
5417A, 
5417A-WG  0.80 (20,3)  1.84 (46,7)  6.75 (171)  7.50 (191)  6.93 (176) 
0.80 - 1.04 
(20,3 - 26,4) 
5418A, 
 5418A-WG  0.80 (20,3)  1.84 (46,7)  6.75 (171)  7.50 (191)  7.83 (199) 
0.80 - 1.08 
(20,3 - 27,4) 
       Table 2 
D
1
L 
D
1
D
2









