Cut Sheet

3M™ Cold Shrink QS-III Inline Splice Kits 15 kV
5415A, 5416A, 5417A, 5417A-WG, 5418A and 5418A-WG
8 of 9 78-8125-9882-5 Rev C
Connectors for QS-III Splices
The QS-III Cold Shrink Splice kits are designed to be used with 3M™ Scotchlok™ Connectors 10000, 11000, and 20000
Series, 3M™ Connectors CI-Series, or other UL listed inline compression connectors that fit within the dimension limits
listed in the 3M™ Connector Dimensional Requirements Table 2. In addition, the following transition connectors may be
used:
Kit Number
Conductor
Sizes
(AWG
or kcmil)
Homac
Connectors
Burndy
Connectors Mac Products
5415A
2 to 1
YRB25U2
2 to 1/0
SAC1/0R2
YRB25U2
MLCR
1/0-2
2 to 2/0 SAC2/0R2
1/0 to 3/0 SAC3/0R1/0 YRB27U25
MLCR
3/0-1/0
2/0 to 3/0
YRB27U26
2 to 4/0 SAC4/0R2
1/0 to 4/0 SAC4/0R1/0
2/0 to 4/0 SAC4/0R2/0 YRB28U26 MLCR 4/0-2/0
3/0 to 4/0
5416A
4/0 to 250 SAC250R4/0 YRB29U28 MLC 250 + AAR 250-4/0 Adapter
4/0 to 300 SAC300R4/0
4/0 to 350 SAC350R4/0 YRB31U28 MLCR 350-4/0
250 to 350 SAC350R250 YRB31U29 MLC 350 + AAR 350-250 Adapter
300 to 350
5417A
5417A-WG
350 to 500 SAC500R350 YRB34U31 MLC 500 + AAR 500-350 Adapter
350 to 600 YRB36U31
500 to 600 YRB36U34
350 to 750 SAC750R350 MLC 750 + AAR 750-350 Adapter
500 to 750 SAC750R500 YRB39U34 MLCR 750-500
5418A
5418A-WG
500 to 750 SAC750R500 YRB39U34 MLCR 750-500
500 to 1000 MLCR 1000-750 + AAR 750-500 Adapter
750 to 1000 MLCR 1000-750