Installation Manual

Industrial Loadbreak Elbow
200 A
5, 8, and 15 kVClass
5810 Series
Installation Instructions
1.0 General
The 3M
Industrial Loadbreak Elbow connector is a fully-
shielded and insulated plug-in termination for connecting
underground cable to transformers, switching cabinets and
junctions equipped with loadbreak bushings. The elbow
connector and bushing insert comprise the essential
components of all loadbreak connections.
The coppertop (bimetal) compression connector is a
standard item to transition from the cable to the loadbreak
probe. An aluminum crimp barrel is inertia-welded to a
copper lug. The aluminum barrel makes the connector
easy to crimp and the copper lug ensures a reliable, tight,
cool operating connection with the loadbreak probe.
2.0 Installation
Cable stripping and scoring tools, available from various
tool manufacturers, are recommended for use when
installing loadbreak elbows. After preparing the cable and
installing shield adapter, the elbow housing is pushed onto
the cable. The loadbreak probe is threaded into the
coppertop connector using the supplied installation tool or
an approved equivalent. Use a shotgun stick to perform
loadmake and loadbreak operations. (See page 10 for
operating instructions.)
Kit Contents:
Elbow Body
Coppertop Compression Connector
Loadbreak Probe
Probe Installation Tool
Silicone Lubricant
Cold Shrink Jacketing Tube
Mastic Strips (3 ea.)
Ground Braid Assembly
Constant Force Spring
CC-3 Cable Cleaning Pads
Installation Instructions
The 5810-CA and 5810-CB Series kits contain the
following additional materials:
Cable Adapter
Silicone Lubricant
Supplemental Installation Instructions
These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide directions for meeting every
contingency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for the user’s
purpose, please contact your 3M sales representative.
Figure 1.
Illustration of a completely assembled 15 kV loadbreak elbow,
shown on tape shielded cable.