Cut Sheet

4
78-8124-5454-0-C
Table 5
Current Ratings and Characteristics
Current ratings and characteristics are in accordance with ANSI/IEEE Standard 386.
Description (600 A Interface) Amperes
Continuous 600 A rms
24 Hour Overload 1000 A rms
Short Time 40,000 A rms symmetrical for 0.20 s
27,000 A rms symmetrical for 4.0 s
Table 6
Typical Splice Dimensions
Splice Assembly Dimension “A” (inches/mm)
Dead End 11.10 (282)
2-way Splice 19.80 (503)
3-way Splice 28.10 (714)
4-way Splice 36.30 (922)
Equipment Connection 9.75 (248)
Table 4
Voltage Ratings and Characteristics
Voltage ratings and characteristics are in accordance with ANSI/IEEE Standard 386.
Description kV
Standard Voltage Class 25
Maximum Rating Phase-to-Ground 15.2
ac 60 Hz 1 Minute Withstand 40
dc 15 Minute Withstand 78
BIL and Full Wave Crest 125
Minimum Corona Voltage Level 19