Cut Sheet
7
78-8124-5454-0-C
For Dead ending shielded power cable. For future add-on
capability with 3M Modular Splicing System
For connecting to 600 Amp apparatus bushing
Adapter Kit Selection Charts (one kit required for each cable being connected)
REVIEW COPY
KIT NO.
5815-B1
5815-B2
5815-B5
5815-B6
5815-B7
5815-B10
5815-B12
5815-B15
5815-B17
5815-B23
5815-B29
5815-B35
5815-B40
5815-B43
5815-B45
5815-B46
Compact
/Solid
4/0
250
Table 9
5 & 8 KV Class
NOTE: Final Kit selection is based on CABLE INSULATION DIAMETER.
Stranded
3/0
4/0
250
350
500
750
1000 Al
Stranded
2/0
3/0
4/0
250
350
500
750
1000 Al
Stranded
2/0
3/0
4/0
250
350
500
750
1000 Al
Stranded
2/0
3/0
4/0
250
350
500
750
1000 Al
Compact
/Solid
4/0
250
Compact
/Solid
3/0
4/0
250*
Compact
/Solid
3/0
4/0
250*
5 kV
(AWG/kcmil)
8 kV
(AWG/kcmil)
100%
(90 mils)
100%
(115 mils)
133%
(140 mils)
133%
(115 mils)
*NOTE: Check ACTUAL CABLE INSULATION DIAMETER to verify correct kit selection.
INSUL.
DIA. RANGE
Inches (mm)
0.640 – 0.760
(16.3 – 19.3)
0.720 – 0.845
(18.3 – 21.5)
0.785 – 0.970
(19.9 – 24.6)
0.910 – 1.065
(23.1 – 27.1)
0.980 – 1.140
(24.9 – 29.0)
1.080 – 1.280
(27.4 – 32.5)
1.220 – 1.420
(31.0 – 36.1)
1.360 – 1.560
(34.5 – 39.6)
5815-D
Dead End
Modular Kit
5815-B
Series
Adapter Kit
5815-B
Series
Adapter Kit
5815-E
Modular
Equipment Kit
A
A