Installation Instructions

May 2010
78-8129-9276-2-A
3M
Direct Bury Splice DBR/Y-6
Instructions
600 V Maximum
Application Temperature 32°F–120°F (0°C–49°C)
UL Listed, File No. E102356
UL Standard 486D
CAUTION
Working around energized systems may cause serious injury or death. Installation should
be performed by personnel familiar with good safety practice in handling electrical
equipment. De-energize and ground all electrical systems before installing product.
1.0 Installation Instructions
1.1 Strip insulation 3/4" (20 mm).
3/4"
(20 mm)
1.2 With wire ends even, insert wires into the connector
and tighten until secure.
1.3 Insert the connector all the way into the tube until
the connector rests on the bottom.
Note: If having difficulty getting the twist-on connector
down into the tube when using small gauge wires,
use a thin, non-conductive object to push the
connector to the bottom of the tube. Upon removal
of the object, ensure that no voids or water paths
remain in the grease.