TEST MODE
I. Definitions:
Switch Terminal Markings
Normally Open, NO or N/O: When the switch is not in an active state (plunger not depressed, switch not
thrown, spring not tensioned). The resistance between the common terminal
and the NO terminal, when measured with an Ohm-meter should be open.
Normally Closed, NC or N/C: When the switch is not in an active state (plunger not depressed, switch not
thrown, spring not tensioned). The resistance between the common terminal
and the NC terminal, when measured with an Ohm-meter should be closed.
Common or COM The terminal which has a common connection to either the NO or NC terminal
when the switch is not active, and to the other terminal when the switch is a
activated. This contact should always be used to connect the system ground.
Most mechanical switches whether they are NO or NC have both terminals available for connection.
II. General MCU Test Mode Operation:
1. Place unit in TEST mode by holding the POST button while powering the unit.
2. See page T7 for software flow diagram.
3. If unit is tilted beyond 50 degrees for 2 seconds it will beep 1 time.
4. If unit senses continuos motion for 15 seconds it will beep 2 times.
5. If there is a transition of light (dark to light, or light to dark) the unit will beep 3 times (if light sensor is
installed and active).
6. If the unit senses thermal shock & senses temperature below 0 deg C or above 70 deg C the unit will beep 5
times.
7. If a sensor is activated (DOOR, BOLT, ALARM SUITE, BREACH, et al) the unit will display a hex code on
the LEDs for the highest priority sensor which is active. This process can take ~ 1 second from event to
display.
Test Mode uses a hierarchy to manage multiple active inputs. This is not an assignment of importance;
however, it will mask the lower priority inputs until higher priority inputs are cleared. See Table 3 for
error code resolution.
Available Sensor Array Cable Inputs: Terminal Block Inputs: (Referenced top-up, left to right)
Pin 1 Manual Fire NC/Breach Pin 1 Generic NC Input #2
Pin 2 Generic NO Input #2 Pin 2 Ground
Pin 3 Power Loss V++ Pin 3 Power Loss V++
Pin 4 Ground Pin 4 Manual Fire NC/Breach
Pin 5 ATM Door Switch Pin 5 ATM Door Switch
Pin 6 All Safe Signal Pin 6 Ground
Pin 7 Generic NC Input #1
Pin 8 Generic NO Input #1
8. If no sensors are active the unit will blink the red LED ~ 1 time per second: When the unit is received it will
blink its red LED 1 time per second. (
, , )
9. Power Loss detection can be enabled by applying 5 VDC to the power loss input on the terminal block or the
sensor array cable.
10. Sensor array input NC_1 detection can be enabled by shorting pin 7 of the sensor array cable to pin 4.
11. Beeping and LED display can occur simultaneously.