User's Manual

Octopus ATM Defense System
Installation and Operation Guide
PageT4
Priority LED Code HEX Active Sensor Detected Expected Input w/ system deactivated.
1 1101 0xD ATM_DOOR Normally Open contact input from door
switch.
2 1100 0xC Generic NC input 2
(Terminal Block Only)
Open contact input when bolt is open or
system is in standby – no alarm exists
3 1110 0xE Generic NO input 2 Closed contact input when system is in
standby – no alarm exists
4 1011 0xB Generic NO input 1 Closed contact input when system is in
standby – no alarm exists
5 0101 0x5 All Safe Signal Open contact input when system in standby
for test mode only. Signal transition from
closed to open condition activates this input.
LEDs will blink on for ~ 1 second every time
a transition occurs.
6 1111 0xF Manual Fire Closed contact input Closed contact input
when system is in standby – no breach.
7 1001 0x9 Generic NC input 1 Open contact input when system is in
standby – no alarm exists. Must be activated
to display.
8 1010 0xA Power Loss +5 VDC and ground reference. Must be
activated by applying +5VDC to terminal
block pin 3 and ground. LEDs, will blink
on/off in 1 second intervals while power is
not connected,
Table 3. Test Mode LED Display Table.
= Red LED on, = Red LED off , = Green LED on, and = Green LED off.
9. Once the unit is properly configured, display of 0x9 hexadecimal , ( , 1001) to indicate that
Generic NC input 1 is not closed or by blinking LED . With the inputs in this condition, an input / output test
can be performed and verified using the LEDs.
10. Activate any sensor input (close if open, open if closed) and the view the hex code associated with that sensor.
Use Table 3 to identify the highest priority sensor which is active.
If the Manual Fire is activated it will close the alarm contacts so that the siren or external strobe can be tested.
11. Tilt the unit beyond 50 degrees and hear 1 beep to indicate tilt.
12. Shake, tap, or vibrate unit for 15 seconds and hear 2 beeps to indicate motion.
13. Cover or expose the light sensor (if available) and hear 3 beeps to indicate light transition.
14. Heat or freeze the unit and here 5 beeps to indicate thermal violation.
Unit may be released out of test mode by:
a) Removing/re-installing the power jumper while not pressing the POST button
b) Pressing the POST button.
c) Waiting for it to time out ~ 10 minutes.
15. When released from test mode, the unit will beep 10 times to notify operator of mode transition.
16. When the unit leaves test mode it will return to standby mode if the door sensor is not active. If the door
contact is active, the unit will progress to discovery, error testing, and arming the system.
***For Level II (Canada operation) Functionality both the Generic NC input # 2 (bolt position) and the door
contact must be active (closed) to arm the system.