Instruction manual

3. External Dimensions
Unit : mm
4. General Specifications
Voltage requirement DC 24 V +10%, -15%
Power requirement Approximately 6 W
Sensor power supply 5V 350 Ω sensor. Up to four sensors can be connected.
Operating conditions -10 °C to +50 °C, Max 85 %RH (no condensation)
External dimensions 35.3 × 110.0 × 101.3 mm (W×H×D)
Mass Approximately 180 g
5. Panels
5.1.
Monitor
The monitor displays measurement data and settings with 7 segments and negative
sign. The decimal point is specified in function mode.
5.2.
Connections
When connecting and removing the cables, push the buttons with a driver etc.
We recommend use of pole crimp terminals for the tips of cables.
-1- -2-
-
3
-
-
4
-
Perform stable measurement in the calibration to prevent measurement error.
During a stable measurement, the LED lights.
The decimal point flashes in calibration mode.
6.1.
Span Calibration using Mass
Preset a unit, decimal point, minimum division and weighing capacity in function
mode. The span calibration is performed using mass of the weighing capacity.
When and a number are displayed, an error has occurred. Refer to
"Calibration Errors" for details.
The flashing decimal point means "no weighing value".
Before the calibration, turn on the AD4430B more than 10 minutes so as to
avoid temperature drift (change).
Step 1 When turning off the display, press and hold the
key and press the
key ( + key).
Then
of calibration mode is displayed.
Step 2 Press the key to enter calibration mode.
is displayed. When returning to
weighing mode, press the key.
6.1.1. Zero Calibration
Step 3 Press the key to display .
When skipping zero calibration, press the
key and proceed to step 5.
Step 4 Place nothing on the weighing pan.
Confirm that the
LED is lit and press the
key. Then is displayed for 2
seconds. When canceling span calibration and
returning to weighing mode, press the
key twice.
6.1.2. Span Calibration
Step 5 When is displayed, press the
key. The current span mass is displayed. A
figure for the mass flashes. Specify a new value
for the mass using the
and keys.
When canceling span calibration and returning
to weighing mode, press the
key twice.
Step 6 Place the mass on the weighing pan.
Confirm that the
LED is lit and press the
key. Then is displayed for 2
seconds.
Step 7 When
is displayed, remove the mass
from the weighing pan. When repeating span
calibration, press the
key.
Step 8 Press the
key. Then is
displayed and calibration data is stored in the
FRAM of the AD-4430B.
Step 9 Press the
key to return to weighing mode.
6.2.
Calibration Errors
Display
Cause Treatment
Resolution (Weighing
capacity / minimum division)
exceeds the limitation.
Make the minimum division greater or make the
weighing capacity smaller. The specified value
depends on specifications of the weighing system.
The voltage in zero
calibration is too large.
The voltage in zero
calibration is too small.
Check the load cell rating and connection. When
nothing is wrong with the rating and connection,
adjust the load cell output. When the load cell or
A/D converter may be the cause of error, confirm
this by using the check mode.
Mass value exceeds the
weighing capacity.
Mass value is too light for
calibration.
Use an appropriate calibration weight and
calibrate again.
Sensitivity of the load cell is
too small.
Use a load cell with higher sensitivity or make
the minimum division greater.
The polarity of the load cell
output is reversed.
Check the load cell connection.
The output of the weighing
capacity is out of range.
Use a load cell with a greater rating or make the
weighing capacity smaller.
5.3.
Status Indicator
LED Meaning
Gross : LED lights when indicating gross value.
Net : LED lights when indicating net value.
Hold : LED lights when the hold function operates.
Stable : LED lights when the current weighing value is stable.
Zero : LED lights when the weighing value is center zero.
This LED works by selected function at .
5.4.
Keys
Operation Function
The display switch between gross and net in factory setting.
"The zero key" to perform the zero adjustment in weighing mode.
The key to change a selected item or move a flashed figure.
"The tare key" that displays zero for net weighing.
The key to select parameter or increase number in setting mode..
Press the key to turn on the display in standby (OFF mode).
Press and hold the key to turn off the display in weighing mode.
In the setting mode, this key to store new settings. "the enter key".
Function key can be selected the function and use in weighing mode.
The return key or "the escape key" in setting mode.
+
Proceeds to function mode in weighing mode.
+
Proceeds to check mode in the function mode.
+
Proceeds to calibration in standby (OFF mode).
5.5.
Power Supply Connector
+24 V
............
D.C. Power Supply +24 V terminal.
0 V
................
D.C. Power Supply 0 V terminal.
Cautions when wiring the power cables
Turn off all of the power supplies of devices related to the AD-4430B. Separate the
power cable of the AD-4430B from other power cables and cables with electrical noise.
5.6.
Sensor Terminals Of Load Cell
SIG-
.............
The (-) input terminal of signal that is outputted from load cell.
SIG+
.............
The (+) input terminal of signal that is outputted from load cell.
EXC-
...........
The (-) output terminal to load cell excitation voltage (-).
SEN-
...........
The (-) input terminal for sensing input (-).
SEN+
...........
The (+) input terminal for sensing input (+).
EXC+
...........
The (+) output terminal for load cell excitation voltage (+).
SHLD
...........
Connect shield of sensor cable.
5.7.
BCD Connector
The circuit of BCD is isolated from the
D.C. power supply and load cell
circuit.
Supply D.C. +24 V between BCD
PWR+24V terminal and COM
terminal.
5.8.
Operation Mode
Function mode (In weighing mode, + )
The condition of the AD-4430B can be updated and be stored.
Check mode (In function mode, + )
The mode to check the AD-4430B.
Calibration mode (When display is turned off, + )
The mode to calibrate zero point and span of the AD-4430B using span mass.
6. Calibration
The AD-4430B measures the voltage of the sensor and displays it. Calibration mode
calibrates (adjusts) so as to measure and display correctly.
Specify decimal point (
), minimum division ( ) and weighing capacity
(
) in function mode.
Adjust the input voltage of zero point (
), the input voltage of span voltage
(
) and mass corresponding to span voltage ( ) in calibration mode.
The digital calibration can be performed in function mode.
Pull down when removing.
Guide for rail
Hook for rail
Vent
Vent
5.1. Monito
r
5.3. Status Indicato
r
5.4. Keys
5.6. Sensor Terminals
Of Load Cell
5
.
5
. Power Supply
Connecto
r
5.7. BCD Connecto
r
AD-4430B
DIN Rail Weighing Module
Simplified Instruction Manual
1WMPD4002677
1.1.
This Manual
This manual describes how the product works and how to get the most
out of it in terms of performance. Read this manual thoroughly before
using the product and keep it at hand for future reference.
Refer to the instruction manual on the A&D home page.
URL: http://www.aandd.co.jp/
Product specifications are subject to change without any obligation on
the part of the manufacturer to notify of changes.
This manual is subject to change without notice at any time to improve
the product. No part of this manual may be photocopied, reproduced,
or translated into another language without the prior written consent of
the A&D Company, limited.
2013 All rights reserved.
2. Cautions
2.1.
Installation and Precautions
The module complies class A computing device pursuant to Subpart J of Part 15
of FCC rules. (FCC = Federal Communications Commission in the U.S.A.)
The module complies the statutory EMC (Electromagnetic Compatibility)
directive 2004/108/EC and the Low Voltage Directive 2006/95/EC for safety of
electrical equipment designed for certain voltages for European Directives.
The module is a precision electronic instrument. Handle it carefully.
Avoid vibration, shock, extremely high temperature and humidity, direct sunlight,
dust, splashing water and air containing salt or sulfurous gases.
Avoid places where inflammable gases or vapors are present.
The operating temperature is -10°C to +50°C (14°F to 122°F).
Ground the module and DIN rail.
Keep cables away from power cables and other sources of electrical noise.
Use a stable DC24 V power source that does not include step down voltage
and noise.
Do not share the earth ground line and power line with other electrical power
equipment.
When extending the load cell cable, separate it from the power cable and
electrical cables with much noise.
Do not turn on the module until installation is complete. The module is not
equipped with a switch to turn off.
Use a shielded load cell cable.
Do not connect more sensors than the allowable number noted in the
specifications.
2.2.
Cautions During Use
The AD-4430B is a precision instrument that measures microvolt output from
sensors. Prevent noise sources such as power lines, radios, electric welders or
motors from affecting the instrument.
Do not disassemble the AD-4430B.
In all hold modes, the hold data is saved digitally, so there is no drooping of the
value displayed on the display panel or the analog output. Note that the hold
function is disabled when the AD-4430B is disconnected from the power supply.
11
35.3
20
°
39.4
(2.5) 100 1.3
34.5
36.1
28
5.5
Ex. : Pole crimp terminal
The load cell cabl
e
Power lin
e
Push buttons when connecting and
removing the cables.
A
ccessory connector for power
supply terminal.
Push buttons when connecting and
removing the cables.
key
Key to store data
key
In measurin
g
key
key
key
key
key
key
Remove
mass
Place mass
Example
Example
In measurin
g
Span
calibration
Zero
calibration
Calibration
mode
LED
LED

Summary of content (2 pages)