Operation with only one supply frequency inverter
MICROMASTER 420 / 440 – DC link coupling between several
Frequency inverters
Example 2:
3-ph. 380-480V AC 50/60Hz
Line fuses
3 x 10A
Line
contactor
Line reactor
Inverter
Copyright © Siemens AG 2005 All rights reserved
M
3 ~
Motor
M
3 ~
M
3 ~
Motor Motor
MM440
1,5kW
MM440
0,55kW
MM420
0,55kW
L1
L2
L3
PE
PE PE PE
PEPEPE
Fig. 2-3: DC link coupling of a 1.5kW MM440 frequency inverter with an
0.55kW MM440 and a 0.55kW MM420
In this particular case, the DC link does not have to be fused, because:
o All of the frequency inverters require line fuses of 3x10A and these are
used at the input of the supply inverter.
o The total DC link current (summed) of the two connected frequency
inverters each with 0.55kW is, according to Table 2-2 I
DCtot
= 2*2A = 4A.
For this current, a cross-section of 1.5mm² (routing type B2, 2
conductors conducting current, 40°C ambient temperature) can be used
which are adequately protected using the 3x10A line fuses.