Instruction manual

35
Servicing should only be performed by a Qualied Service Agent
ADJUSTMENT
There must be sufcient load to operate the boiler/water heater at high re to perform the following adjustments. Start the boiler/water
heater and observe proper operating parameters for the system.
Required Tools:
TORX
®
T40 or 5 mm hex wrench
3 mm or 7/64 inch hex wrench
Combustion analyzer
These boilers/water heaters are equipped with a Honeywell combined gas/air control and gas safety shut off control valves. The
valve functions in parallel with the variable speed combustion blower to supply the correct gas air ratio for optimum performance and
efciency. The combustion blower speed is controlled automatically and determines the amount of negative pressure experienced
by the gas safety shut off/control valves. The gas/air regulator adjusts gas ow to maintain the proper pressure at the outlet nozzle
of the associated valve.
SETTING OF THE TEST MODE
On the Burner Home screen, select any individual boiler/water heater which will guide to Burner Information screen.
Click on Operation button, and under the Modulation Menu, set the required Firing rate (High/Low) by setting the RPM.
On the Firing Rate page, set the Firing rate RPM by selecting the Manual in Run check box.
FIGURE 22. BURNER HOME SCREEN FIGURE 23. BURNER INFORMATION SCREEN