LOCAL OPERATOR INTERFACE: DISPLAY SYSTEM
FIGURE 27. S7999D DISPLAY SYSTEM
The S7999D is a microprocessor-based touchscreen Operator Interface (OI) display that provide an operator interface for monitoring
and conguring parameters in the Burner Control system.
The S7999D is used to monitor an individual burner on the XB Boilers/XWH Water Heaters applications in a lead/lag arrangement. It
consists of 2 RS485 ports (COM 1 & COM 2) and USB port. The S7999D display can be ush front or behind mounted into a panel
cutout. Wiring connections to the S7999D are through a removable 8-pin wiring connector.
FEATURES
Individual boiler/water heater status, conguration, history, and diagnostics.
Allows conguration and monitoring of the Burner Control Controls burner control sequence, ame signal, diagnostics, historical
les, and faults.
S7999D OI Display only:
Allows switching view between multiple burners.
Allows viewing Lead-Lag Master.
Real-time data trending analysis and transferring saved trend data to Excel spreadsheet.
7” 800 x 480, 24 bit high resolution color LCD touch screen for clarity.
Audio output with integral speaker for sound output.
Adjustable backlight control.
Real time clock with coin-cell battery back up (CR2032).
S7999D has Black Border.
Volume control.
Screen Capture function to capture screen images.
USB port for le transfers and software updates
2 RS-485 (COM1 & 2) ports for Modbus™ interface to Burner controls and BAS Gateway.
Windows® CE 6.0 Operating System.
8-pin connector, back-up battery and mounting hardware are provided.
SPECIFICATIONS
1. Electrical Ratings:
Input Voltage: 18 – 30 Vac (24Vac nominal), 50/60 Hz
Input Current: 500 mA max.
Power consumption: 12W max.
2. Operating Temperature: -4 to 158 ºF (-20 to 70 ºC)
3. Storage/Shipping Temperature: -22 to 176 ºF (-30 to 80 ºC)
4. Humidity: 90% RH, non-condensing.
5. Enclosure rating: IP10 / NEMA 1