13.2 Troubleshooting table for general errors
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
General errors
Symptom Cause Solution Remark
Gas smell Gas leak
Close the main gas valve immediately.
Do not operate any switches.
No naked flames.
Ventilate the boiler room.
Contact your installation engineer or local gas company
immediately.
Display is off Appliance is turned off Start the appliance up (9 "Starting and running")
No supply voltage
present
1. Check if the isolator is ON.
2. Check that there is power to the isolator.
3. Check whether the ON/OFF switch of the electronic controller is
ON (position I).
4. Check whether there is power to the electrical connector block.
5. The measured voltage must be 230 VAC (-15%, +10%).
See the ADMR electrical diagram (17 "Appendices")
If the error persists, consult your installation engineer.
Defective fuse(s) Replace fuse(s) To replace the fuses, you must contact your installation engineer.
Water leakage Leakage from a water
connection (threaded)
Tighten the threaded connection If the leak persists, consult your installation engineer
Leakage from another
nearby water appliance
or pipe segment
Trace the leak
Leakage from the
appliance's tank
Consult the supplier and/or manufacturer
Condensation Before drawing (too much) tap water, wait until the water in the
boiler has reached the set temperature.