Operation Manual
is
Instruction manual ADMR 70
S14 (blocking error)
Short circuit in flue gas
sensor 1
Short circuit in flue gas
sensor circuit
Replace the flue gas sensor
(2)
and lead. To replace the necessary parts, you must contact your installation
engineer
S15 (blocking error)
Short circuit in flue gas
sensor 2
Short circuit in flue gas
sensor circuit
Replace the flue gas sensor
(2)
and lead. To replace the necessary parts, you must contact your installation
engineer
F01 (blocking error)
Defect in power supply
circuit
Live and neutral
connected wrong way
round
Connect live and neutral correctly (3.10 "Electrical connection")
;
the appliance is phase-sensitive
See the ADMR electrical diagram (17 "Appendices")
Condensation on the
flame probe
1. Disconnect the lead at the flame probe
2. Ignite the appliance three times, with an interrupted ionisation
circuit
3. Reconnect the ionisation lead to the flame probe
4. Ignite the appliance again
5. The repeated ignition attempts will have caused the
condensation to evaporate
If errors persist, contact your installation engineer
Floating neutral Install an isolating transformer (3.10.5 "Connecting an isolating
transformer")
Contact your installation engineer to have an isolating transformer
installed
Symptom Cause Solution Remark