-Clearances for rooop terminaons-
Follow all local and national codes in regards to proper termination clearances. In the
absence of such codes, the clearances below must be met. Local codes supersede these
clearances. Failure to observe this warning may result in severe personal injury or death.
WARNING
Exhaust terminations must be at least 1 ft (305 mm) away from any obstructions.
Minimum spacing between multiple terminals:
intake terminals: 1 ft (305 mm) spacing between each
exhaust terminals: 1 ft (305 mm) spacing between each
The exhaust termination must be a horizontal distance of at least 2 ft (610 mm) from a
wall or surface unless specified differently by local code.
Failure to observe this warning may result in severe personal injury or death.
WARNING
Angled roof termination
Ancipated snow level
2  (610 mm) min.
1 
(305 mm)
min.
1 
(305 mm)
min.
1 
(305 mm)
min.
Exhaust
Intake
Multiple flat roof terminations













Exhaust
Exhaust
Intake
Intake
Flat roof termination
Ancipated snow level
3  (914 mm) min.
1 
(305 mm)
min.
1 
(305 mm)
min.
Exhaust
Intake
Multiple angled roof terminations
1 
(305 mm)
min.
1 
(305 mm)
min.
3 
(914 mm)
min.
1 
(305 mm)
min.
1 
(305 mm)
min.
Ancipated snow level
2 
(610 mm)
min.
1 
(305 mm)
min.
Exhaust
Exhaust
Intake
Intake