FOR YOUR SAFETY, READ BEFORE INSTALLATION:
Do not install the water heater or vent
termination next to a dryer or dryer vent. The
water heater environment must be free from
any source of airborne debris that can be
trapped inside the water heater.
Installaon
Installaon Manual
Water heater vent terminator must be at least 2 ft
(61 cm) away from an inside corner.
WARNING FOR INSTALLATIONS
USA: 1 (30 cm) min.
Canada: 3  (91 cm) min.
USA: 1 (30 cm) min.
Canada: 3  (91 cm) min.
USA: 1 (30 cm) min.
Canada: 3  (91 cm) min.
USA: 12 in. (30 cm) above grade and
above ancipated snow level
Canada: 12 in. (30 cm) above grade
Ancipated snow level
Ensure that you meet the minimum clearances shown below for a direct vent termination:
Inside
corner
2 ft
(61 cm)
min.
Improper installation will void the warranty and may cause damage to the water heater.
NOTICE
WARNING
 Do not install the water heater and its termination where water, debris or
flammable vapors may get into the water heater and flue terminal.
 Do not have the vent terminal pointing toward any opening into a building.
 Do not locate your heater in a pit or location where gas and water can
accumulate.
 Failure to observe these warnings could result in carbon monoxide poisoning
or death.