Technical Documents

CAPACITY, INPUT AND RECOVERY
MODEL
NUMBER
BTU
INPUT
PER
HOUR
Gallons
or
Litres
TANK
SIZE
FIRST
HOUR
RATING
100°F
RISE
GPH
or
LPH
RECOVERY-GALLONS
PER HOUR AT
100°F
TEMPERATURE
RISE
40°F
100°F 140°F
4°C
56° C
78°C
BTP 540A
BTPV 540A
540,000
US. Gallons 85 583 GPH 1309 523 374
Litres 321.7 2206.7 LPH 4954.6 1979.6 1415.6
BTP 650A
BTPV 650A
650,000
US. Gallons 85 690 GPH 1579 630 450
Litres 321.7 261 1 .7 LPH 5976.5 2384.6 1703.3
BTP 740A
BTPV 740A
740,000
US. Gallons 85 778 GPH 1794 718 512
Litres 321.7 2944.7 LPH 6790.3 2717.6 1937.9
Based on 80% Thermal Efficiency. To compensate for effects of high altitude above 2,000’,
recovery ratings should be reduced approximately 4% for every 1,000 feet above sea level.
Current Draw (120V,60Hz, 1 Phase): 6.0 Amps
DIMENSIONS AND WEIGHT - ALL MODELS
Inches
or CM
DIMENSIONS
GAS
CONN.***
SHIPPING
WEIGHT
ABCDE FGH1
Inches 80-3/4 73 32-1/4 9 26-1/2 26-1/2 93 29-1/2 48-1/2 1” 950 Lbs.
CM 205.1 185.4 81.9 22.9 67.3 67.3 236.2 74.9 123.2 - 43 1.8 Kg
*D dimension is for atmospheric vent size (BTP models).
**E dimension is for direct and sidewall vent size (BTPV models).
***Minimum gas supply pipe is 1-1/2”. See Reference Manual, Table 7 for gas supply pipe size. BTPV heaters are available in Natural gas only.
SUGGESTED SPECIFICATION
For Technical Information and Automated Fax Service, call 800-527-1953. A. O. Smith Corporation reserves the right to make product changes or improvements without prior notice.
Commercial Gas Water Heaters
Page 2 of 2
www.hotwater.com
AOSCG11000
8” WC Minimal Gas Supply
Pressure Required For
All Models!
®
Revised October 2012
Water heater(s) shall be A. O. Smith Model ________________or equal, with maximum storage capacity of 85 gallons, an input rating of _________BTU/Hr., a
recovery rating of ___ GPH at 100º F temperature rise, and minimum thermal efficiency of 80%. Heater(s) shall meet the thermal efficiency and standby loss require-
ments of the U.S. Department of Energy and current edition of ASHRAE/IESNA 90.1, comply with SCAQMD Rule 1146.2 (BTPV 540 and 650 only) and other air quality
management districts with similar requirements for s. In addition, heater(s) shall: 1) Include a powered gas burner, redundant main gas valves, gas pressure regulator
and flame inspection port. 2) Include a e. and be so marked for a maximum working pressure of 160 PSI. 5) Have a glass-lined steel tank with multiple anodes for
corrosion protection, and polyurethane foam insulation. 6) Tank shall have a 3-year limited warranty against corrosion as outlined in the written warranty. Venting: BTP
heater(s) shall be supplied with a Barometric Draft Regulator for conventional atmospheric venting. BTPV heater(s) shall be supplied with an optional vent kit allowing
for horizontal sidewall venting or direct venting. Burner and Controls: Burner(s) shall be pre-mix design, with internal FGR and thermal cut off, separate spark pilot
ignition system, integral blocked flue sensor, glass view port, main gas regulator, automatic gas valve, manual test cock and manual gas shutoff. Burner(s) must be
factory-installed, tested and started by an A. O. Smith Authorized BTP Start-up Agent before being placed into operation.