Installation Guide

GENERAL INFO
Point-of-Use Models
(For potable water heating only. Not for space heating.)
NOTICE: Models sorted by Voltage, then by Wattage per Element.
Model Recommended
Breaker Size
(Amps)
Voltage Number
of
Elements
Wattage
per Element
(KW)
Current per
Breaker
(Amps)
Recommended
Wire Size
*
(AWG)
Element Type
*P**-40-Y 15 277 1 4 14.44 14 Single
*P**-60-Y 25 277 1 6 21.66 10 Single
*P**-73-Y 30 277 1 7.3 26.35 10 Single
*P**-90-Y 40 277 1 9 32.49 8 Single
*
All wiring/conductors must be rated for 90°C or greater.
Follow all code requirements.
Two-Chamber Models
(For potable water heating only. Not for space heating.)
NOTICE: Models sorted by Voltage, then by Wattage per Element.
Model Recommended
Breaker Size
(Amps)
Voltage Number of
Elements
Wattage per
Element (KW)
Current per
Breaker
(Amps)
Recommended
Wire Size
*
(AWG)
Element
Type
*2**-140-X
40 amps each
(2 circuits)
208 2 7 33.65 8 Single
*2**-120-E
60 amps 240 2 6.1 50.83 6 Single
*2**-140-E
60 amps
240 2 7 58.34 6 Single
*2**-160-E
40 amps each
(2 circuits)
240 2 8 33.33 8 Single
*2**-180-E
40 amps each
(2 circuits)
240 2 9 37.5 8 Single
*
All wiring/conductors must be rated for 90°C or greater.