Operating Instructions and Installation Instructions
22
4.2 DRAINING THE SOLAR THERMAL SYSTEM
1. Open the non return valve in the return ball
valve [4] by turning it to position 45º.
2. Connect a heat-resistant hose to the drain
valve [7].
Make sure that the solar uid is collected in a
heat-resistant container.
3. Open the drain valve [7] of the solar pump
station.
4. Open a vent valve that may be present at the
highest point of the solar system.
5. Dispose of the solar uid observing the local
prescriptions.
Danger: Danger of scalding due to hot solar uid!
The escaping medium may be very hot. Place the collecting container so that
people standing nearby are not endangered when the solar thermal system is
being emptied.