Instruction manual
23
CONFINED SPACE
A  conned  space  is  one  whose  volume  is  less  than  50  cubic 
feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input 
rating of all appliances installed in the space.
Openings must be installed to provide fresh air for combustion, 
ventilation and dilution in conned spaces. The required size for 
the openings is dependent on the method used to provide fresh 
air to the conned space and the total Btu/hr input rating of all 
appliances installed in the space.
DIRECT VENT APPLIANCES
Appliances installed in a direct vent conguration that derive all 
air for combustion from the outdoor atmosphere through sealed 
intake air piping are not factored in the total appliance input Btu/
hr calculations used to determine the size of openings providing 
fresh air into conned spaces.
EXHAUST FANS
Where exhaust fans are installed, additional air shall be provided 
to replace  the  exhausted air.  When  an exhaust fan  is installed 
in  the  same  space  with  a  water  heater,  sufcient  openings  to 
provide  fresh  air  must  be  provided  that  accommodate  the 
requirements for all appliances in the room and the exhaust fan. 
Undersized  openings  will  cause  air  to  be  drawn  into  the  room 
through the water heater’s vent system causing poor combustion. 
Sooting, serious damage to the water heater and the risk of re 
or explosion may result. It can also create a risk of asphyxiation.
LOUVERS AND GRILLES
The free areas of the fresh air openings in the instructions that 
follow do not take in to account the presence of louvers, grilles or 
screens in the openings.
The  required  size  of  openings  for  combustion,  ventilation  and 
dilution air shall be based on the “net free area” of each opening. 
Where the free area through a design of louver or grille or screen 
is  known,  it  shall  be  used in  calculating  the  size  of  opening 
required to provide the free area specied. Where the louver and 
grille design and free area are not  known, it  shall be  assumed 
that wood louvers will have 25% free area and metal louvers and 
grilles will have 75% free area. Non motorized louvers and grilles 
shall be xed in the open position.
FRESH AIR OPENINGS FOR CONFINED SPACES
The  following  instructions  shall  be  used  to  calculate  the  size, 
number  and  placement  of  openings  providing  fresh  air  for 
combustion, ventilation and dilution in conned spaces. The 
illustrations shown in this section of the manual are a reference 
for the  openings that provide fresh  air into conned  spaces 
only.  Do  not  refer  to  these  illustrations  for  the  purpose  of  vent 
installation. See Venting section on Page 25 for complete venting 
installation instructions.
OUTDOOR AIR THROUGH TWO OPENINGS
The  conned  space  shall  be  provided  with  two  permanent 
openings, one commencing within 12 inches (300 mm) of the top 
and one commencing within 12 inches (300 mm) of the bottom of 
the enclosure. The openings shall communicate directly with the 
outdoors. See Figure 17.
Each opening shall have a minimum free area of 1 square inch 
per 4,000 Btu/hr (550 mm
2
 per kW) of the aggregate input rating 
of all appliances installed in  the enclosure. Each  opening shall 
not be less than 100 square inches (645 cm
2
).
OUTDOOR AIR THROUGH ONE OPENING
Alternatively a single permanent opening, commencing within 12 
inches (300 mm) of the top of the enclosure, shall be provided. 
See  Figure  18.  The  water  heater  shall  have  clearances  of  at 
least 1 inch (25 mm) from the sides and back and 6 inches (150 
mm) from the front of the appliance. The opening shall directly 
communicate with the outdoors or shall communicate through a 
vertical or horizontal duct to  the outdoors  or spaces that freely 
communicate with the outdoors and shall have a minimum free 
area of the following:
1.  1 square inch per 3000 Btu/hr (700 mm
2
 per kW) of the total 
input rating of all appliances located in the enclosure, and
2.  Not less than the sum of the areas of all vent connectors in 
the space.
FIGURE 17.  OUTDOOR AIR THROUGH TWO OPENINGS
FIGURE 18.  OUTDOOR AIR THROUGH ONE OPENING










