Instruction manual
35
DIRECT VENTING: VERTICAL TERMINATION
Installation  must  comply  with  local  requirements  and  with  the 
National  Fuel  Gas  Code, ANSI Z223.1 for U.S.  installations  or 
CSA B149.1 for Canadian installations.
VENT/AIR TERMINATION LOCATIONS:
Follow these guidelines for locating the vent/air terminations:
1.  Make  sure  the  total  length  of  piping  for  vent  or  air  do  not 
exceed  the  limits  mentioned  in  Table  14  and  Table  15  on 
Page 36. 
2.  The vent  must  terminate at least  3  feet above the  highest 
place in which  the  vent  penetrates  the  roof and at least  2 
feet above any part of a building within 10 feet horizontal. 
3.  The air piping must terminate in a down-turned 180° elbow, 
using a mesh screen, no further than 2 feet (0.6 m) from the 
center of the vent pipe. This placement avoids recirculation 
of ue products into the combustion air stream. 
4.  The vent piping must terminate in an up-turned rain cap as 
shown in Figure 35. When the vent termination uses a rain 
cap  as  illustrated  in  Figure  35,  maintain  at  least  36"  (914 
mm)  above  the  air  inlet.  The  air  inlet  pipe  and  vent  pipe 
can be located in any desired position on the roof, but must 
always be no further than 2 feet (0.6 m) apart and with the 
vent termination at least 1 foot above the air intake. 
5.  Locate terminations so they are not likely to be damaged by 
foreign objects, such as stones or balls, or subject to buildup 
of leaves or sediment and also not blocked or restricted by 
snow accumulation.
6.  If installing both intake air and vent piping in a Direct Vent 
conguration  vertically  through  the  roof;  ensure  that  all 
exterior vertical clearance requirements shown in Figure 35 
are being maintained. These clearances and those cited by 
local and national codes must be maintained.
Note:  On  at  roof  installations  the  intake  air  and  the  vent 
terminations must be a minimum of 24 inches (60 cm) above any 
parapet, vertical wall or structure within 10 feet (3 m) horizontally. 
See Figure 37.
FIGURE 35.  PVC/CPVC AIR/VENT TERMINATION - 
VERTICAL
PREPARE ROOF/WALL PENETRATIONS
1.  Air pipe penetration: 
Cut a  hole  for  the air  pipe.   Size the  air  pipe hole as  close  as 
desired to the air pipe outside diameter. 
2.  Vent pipe penetration: 
Cut  a  hole  for  the  vent  pipe.  For  either  combustible  or 
noncombustible construction, size the vent pipe hole with at least 
a 1/2 inch clearance around the vent pipe outer diameter:
•  7½ inch (178 mm) hole for 6 inch (152 mm) vent pipe
•  8½ inch (203 mm) hole for 7 inch (178 mm) vent pipe 
Insert  a  galvanized  metal  thimble  in  the  vent  pipe  hole  (when 
required by local codes). 
3.  Space the air and vent holes to provide the minimum spacing 
shown in Figure 35 and Figure 36. 
4.  Follow all local codes for isolation of vent pipe when passing 
through oors, ceilings, and roofs. 
5.  Provide  ashing  and  sealing  boots  sized  for  the  vent  pipe 
and air pipe. 
FIGURE 36.  STAINLESS STEEL AIR/VENT TERMINATION - 
VERTICAL
FIGURE 37.  VERTICAL TERMINATION - FLAT ROOF 
CLEARANCES










