Owner's manual
111
1
2
3
4
5
6
METER
OPTIONAL TEMPERATURE 
SENSOR HEADER 
ENCLOSURE INTERNAL
GROUND TERMINAL
-24VDC
+24VDC
POWER
SUPPLY
RL1
+24VDC
DIGITAL OUTPUT #1
RL2
DIGITAL 
OUTPUT #2
-24VDC
+24VDC
-24VDC
MINIMUM LOAD IMPEDANCE 
FOR 24 VDC POWER SOURCE 
IS 160 OHM
ISOLATED POWER
SOURCE #1
(MAXIMUM 40 VDC)
ISOLATED POWER
SOURCE #2
(MAXIMUM 40 VDC)
RL3
ISOLATED 
POWER SOURCE 
(MAXIMUM 60 VDC)
-24VDC
+24VDC
FLOW PULSE OUTPUT
(600 OHM MAXIMUM
LOOP IMPEDANCE)
ANALOG 4-20
MA
OUTPUT #2
RETURN
(-)
(+)
(-)
(+)
ANALOG 4-20
MA
OUTPUT #1
RETURN
OPTIONAL PRESSURE
SENSOR HEADER
GREEN
RED
BLACK
GND
RX+
TX-
TO 9 PIN 
D SUBMIN.
CONNECTOR 
ON PC
5
3
2
RS-232/485 DIGITAL
COMMUNICATION INTERFACE
24 VDC WITH REMOTE 
TRANSMITTER
MAXIMUM CABLE LENGTH UP TO 100 FEET
CONNECT CABLE SHEILD TO THE 
BUILDING PROTECTIVE EARTH
GROUNDING CLAMP METER BODY MUST BE GROUNDED 
TO THE BUILDING PROTECTIVE EARTH PROPERLY
COM.
S2
S1
COM.
S2
S1
USE SUPPLIED
CABLE TERMINATION KIT