Attach the side pieces to the top of the hood 
using the provided screws and  attached the 
side pieces to the end of the unit through the 
flange. 
Apply  silicon  caulking  along  the  top  and 
both sides of the rain hood. Take care to seal 
the top corners where the rain hood attaches 
to the unit. 
Figure 22 - 6-25 and 30 ton 
Closed Rain Hood 
Figure 23 - 6-25 and 30 ton 
Open Rain Hood 
26 and 31-140 ton Units 
Remove the shipping screws from each side 
of the closed hood. 
Lift hood outward and attach the sides of the 
hood to the side of the unit. 
Apply  silicon  caulking  along  the  top  and 
both sides of the rain hood. Take care to seal 
the top corners where the rain hood attaches 
to the unit. 
Figure 24 - 26 and 31-140 ton 
Open Rain Hood 
End Flashing Installation 
On RN Series E cabinet units that are 142” 
wide  (RN-55,  65,  75,  90,  105,  120,  130, 
140)  the  cabinet  width  will  overhang  the 
shipping trailer on each side. 
In order to secure and protect the unit during 
transit the sheet metal end flashings have 
been removed from the unit. The slot created 
at the base of each end of the unit allows the 
unit to set firmly on the trailer deck. 
Sheet metal flashings are shipped loose with 
the  unit  and  once  the unit  is  set  into  place 
the flashings must be installed on each end 
of the unit  to  complete  the  finished  seal at 
the base. The flashings are unit specific and 
designed to cover the slot at each end of the 
unit to prevent water run-off into the curb. 