Electrical 
Verify the unit nameplate agrees with power 
supply. Connect power and control wiring to 
the unit  as  shown  in Figure  I12  and  in  the 
unit  specific  wiring  diagram,  which  shows 
factory  and  field  wiring  and  is  attached  to 
the  inside  of  the  door  of  the  controls 
compartment. 
Route power and control wiring, separately, 
through  the  utility  entry  in  the  base  of  the 
unit.  Do  not  run  power  and  control  signal 
wires in the same conduit. The utility entry 
on  9-25  and  30  ton  units  is  located  in  the 
unit base in the front right hand corner of the 
unit  (compressor  compartment).  The  utility 
entry on 26 and 31-70 ton units is located in 
the unit base in the front left hand corner in 
the unit (controls compartment). The utility 
entry  on  55,  65  and  75-140  ton  units  is 
located  in  the  center  front  of  the  unit.  See 
unit drawing for specific location. 
Figure 27 - Unit Utility Entry 
Figure 28 - Back View of Power Switch 
from Compressor and Control Compartment 
(6-50, 60, and 70 ton Units) 
Electric  shock  hazard.  Before 
attempting to perform any installation, 
service,  or  maintenance,  shut  off  all 
electrical  power  to  the  unit  at  the 
disconnect  switches.  Unit  may  have 
multiple  power  supplies.  Failure  to 
disconnect  power  could  result  in 
dangerous operation, serious injury, 
death, or property damage. 
   WARNING 
Installing  Contractor  is  responsible 
for  proper  sealing  of  the  electrical 
and  gas  entries  into  the  unit  Failure 
to  seal  the  entries  may  result  in 
damage to the unit and property. 
   CAUTION  