Instruction Manual
50 
Figure 29 - Front View of Utility Entry and 
Power Switch from Control Compartment 
(55, 65 and 75-140 ton Units) 
Size  supply  conductors based  on  the unit 
MCA  rating.  Supply  conductors  must  be 
rated a minimum of 75°C. 
Protect the branch circuit in accordance with 
code  requirements.  The  unit  must  be 
electrically  grounded  in  accordance  with 
local codes, or in the absence of local codes, 
the  current  National  Electric  Code, 
ANSI/NFPA  70  or  the  current  Canadian 
Electrical Code CSA C22.1. 
Note: All units are factory wired for 208V, 
230V,  460V,  or  575V.  The  transformer 
configuration  must  be  checked  by  a 
qualified  technician  prior  to  service, 
especially if  unit is  to  be  connected to  a 
208V  or  230V  supply.  For  208V  service 
interchange the yellow and red conductor on 
the low voltage control transformer. 
Red-Black for 208V 
Yellow-Black for 230V 
Wire  power  leads  to  the  unit’s  terminal 
block or main disconnect. All wiring beyond 
this  point  has  been  completed  by  the 
manufacturer  and  cannot  be  modified 
without  effecting  the  unit’s  agency/safety 
certification. 
Supply voltage must be within the min/max 
range  shown  on  the  unit  nameplate. 
Available  short  circuit  current  should  not 
exceed  the  short  circuit  current  rating 
(SCCR) shown on the unit nameplate. 
Three phase voltage  imbalance will cause 
motor  overheating  and  premature  failure. 
The maximum allowable imbalance is 2.0%. 
Voltage  imbalance  is  defined  as  100  times 
the  maximum  deviation  from  the  average 
voltage divided by the average voltage.  
Example: 
(221V+230V+227V)/3  =  226V,  then 
100*(226V-221V)/226V  =  2.2%,  which 
exceeds the allowable imbalance. 
Check  voltage  imbalance  at  the  unit 
disconnect  switch  and  at  the  compressor 
terminal. Contact your local power company 
for line voltage corrections. 
Installing  contractor  must  check  for  proper 
motor  rotation  and  check  blower  motor 
amperage  listed  on  the  motor  nameplate  is 
not  exceeded.  Motor  overload  protection 
may be a function of the variable frequency 
drive and must not be bypassed. 
Three phase voltage  imbalance will 
cause  motor  overheating  and 
premature failure. 
   CAUTION  










