Instruction Manual
54 
Do not use gas piping smaller than unit gas 
connections.  Natural  gas  pipe  runs longer 
than  20  feet  and  propane  gas  pipe  runs 
longer  than  50  feet  may  require  a  larger 
supply  pipe  than the unit connection size. 
Some  utility  companies  may  also  require 
pipe  sizes  larger  than  the  minimum  sizes 
listed. 
Piping Sizing Examples 
A 100 ft pipe run is needed for a 1080 MBH 
natural  gas  heater.  The  natural  gas  has  a 
rating of 1000 Btu/ft
3
 and a specific gravity 
of  0.6  (Obtain  these  values  from  the  local 
gas supplier.) 
BTU
ft
MBH
1000
1080
3
1080 ft
3
/hr 
From the natural gas maximum capacities 
table, at 100 ft and 1080 ft
3
/hr the required 
minimum pipe size is 2”. 
A 100 ft pipe run is needed for a 270 MBH 
propane gas heater. 
270 MBH = 270 kBtu/hr 
From  the  propane  gas  maximum  capacities 
table, at 100 ft and 270 kBtu/hr the required 
minimum pipe size is 1”. 
Inlet and Manifold Pressures 
For natural gas units, the minimum inlet gas 
pressure to the unit is 6” w.c. and maximum 
inlet  gas  pressure  to  the  unit  is  10.5”  w.c. 
For propane units, the  minimum inlet gas 
pressure  to  the  unit  is  11”  w.c.  and  the 
maximum  inlet gas  pressure  to the  unit  is 
13” w.c. A field provided 1/8” NPT pressure 
tap is required to  be installed  in  the piping 
just  upstream of  the shutoff  valve  for  test 
gage connection to allow  checking of  the 
gas supply pressure at the unit. 
A factory installed pressure tap on the outlet 
end of the gas valve can be used to verify a 
manifold pressure of  3.5” w.c. for natural 
gas, or 10.5” w.c. for propane. 
Gas Pressure Regulator & Overpressure 
Protection Device 
A gas pressure regulator must be installed if 
natural  gas  supply pressure  to  the  unit is 
greater  than  10.5”  w.c.  and  less  than  2  psi 
(55.4”  w.c.)  and  if  propane  gas  supply 
pressure is greater than 13”  w.c.  and less 
than  2  psi  (55.4”  w.c.).  Regulators  must 
comply  with  the  latest  edition  of  the 
Standard  for  Line  Pressure  Regulators, 
ANSI Z21.80/CSA 6.22. 
Both  a  gas  pressure  regulator  and 
overpressure protection  device  (OPD) must 
be installed if gas supply pressure to the unit 
is  greater  than  2  psi (55.4”  w.c.)  and  less 
than 5 psi (138.4” w.c.), in compliance with 
ANSI  Z21.80/CSA  6.22.  For  proper  heater 
operation,  pressure  to  the  regulator  MUST 
NOT be greater than 5 psi (138.4” w.c.). 
Piping Supports 
Gas  supply  piping  must  be  supported 
directly at the connection to the unit and at 
intervals  listed  in  the  following  table  with 
metal straps, blocks, or hooks. Piping should 
not be strained or bent. 
Heater should be disconnected from 
the gas supply piping during pressure 
testing  of  the  supply  piping  system 
with pressures in excess of ½ psi. Gas 
valves can be damaged if subjected to 
more than ½ psi. 
   CAUTION  










