Instruction Manual
55 
Table 16 - Gas Piping Supports 
Pipe Size 
Support Intervals 
1/2” to 3/4” 
Every 6 ft 
3/4” to 1” 
Every 8 ft 
1-3/4” or Larger 
(Horizontal) 
Every 10 ft 
1-1/4” or Larger 
(Vertical) 
Every Floor 
Additional Gas Piping Considerations 
Local  codes  will  usually  require  a  field 
provided and installed manual main shutoff 
valve  and  union  external  to  the  unit.  Main 
shutoff valve should be labeled. A drip leg 
should be installed near the unit connection 
to trap sediment and condensate. Pipe joint 
compounds  used  on  all  gas  piping 
connections  should  be  resistant  to  liquid 
petroleum gases. If flexible gas piping to the 
unit,  or  in  the  unit,  must  be  replaced 
connectors  cannot  be  reused,  only  new 
connectors may be used. 
Heat  exchanger  comes  equipped  with  a 
condensate drain which should be plumbed 
to  the  appropriate  drain  according  to  the 
(United  States)  National  Fuel  Gas  Code 
ANSI-Z223.1/NFPA  54  or  the  current 
(Canada)  National  Fuel  &  Propane 
Installation Code CSA B149.1 or B149.2, 
the  International  Building  Code,  and  any 
applicable  local  and  regional  codes  and 
regulations. 
The condensate drain  connection  is  located 
next to the gas entry location. For 6-50, 60 
and  70  ton  units,  the  heat  exchanger 
condensate drain connection from the unit is 
a  5/8” barbed nylon elbow connection. For 
55,  65  and  75-140  ton  units,  the  heat 
exchanger condensate drain connection from 
the unit  is  a  1/2”  PVC  connection.  For  55, 
65 and 75-140 ton units, the heat exchanger 
condensate  drain  can  be  tied  into  the 
evaporator condensate drain, if code allows. 










