Instruction Manual
59 
Freezing Water in the Heat Exchanger 
This  product  contains  one  or  more 
refrigerant-to-water  heat  exchangers.  A 
refrigerant-to-water heat exchanger contains 
refrigerant  in  one  passage  and  water  in 
another passage. Water is subject to freezing 
at  32°F.  When  water  freezes  in  a  heat 
exchanger significant  forces  are  exerted  on 
the components of the heat exchanger where 
the water is confined. 
Failure of the condenser due to freezing will 
allow  water  to  enter  the  refrigerant  circuit 
and  will  cause  extensive  damage  to  the 
refrigerant circuit components. Any damage 
to  the  equipment  as  a  result  of  water 
freezing  in  the  condenser  is  excluded  from 
coverage  under AAON  warranties  and the 
heat exchanger manufacturer warranties. 
Unit  is  capable  of  operating  with  Entering 
Water Temperatures (EWT) as low as 57°F, 
during  the  cooling  mode,  without  the  need 
for  head  pressure  control.  If  the  EWT  is 
expected  to  be  lower  than  57°F  or  a  more 
stable  operation  is  desired,  a  factory 
provided head  pressure  control water valve 
option is available. 
Glycol  solution  should  be  used  if  ambient 
temperatures  are  expected  to  fall  below 
freezing  or  if  the  loop  entering  water 
temperature to the unit is below 50°F while 
operating  in  the  heating  mode  (heat  pump 
units only). Adding glycol to condenser water 
causes  an  increase  in  pressure  drop  and  also 
results  in  a  decrease  in  unit  performance.  A 
minimum  concentration  of  20%  glycol 
solution is recommended. 
Table 17 - Glycol Freezing Points 
% Glycol 
Ethylene 
Glycol 
Propylene 
Glycol 
20 
18°F 
19°F 
30 
7°F 
9°F 
40 
-7°F 
-6°F 
50 
-28°F 
-27°F 
Water  loop  piping  runs  through  unheated 
areas  or  outside  the  building  should  be 
insulated. 
Water Piping 
Installing  contractor  must  ensure  a 
differential  pressure  switch  or  water  flow 
switch  is  installed  between  the  condenser 
water supply  and return connections. This 
sensor  provides  a  signal  to  the  unit 
controller  that  water  flow  is  present  in  the 
refrigerant-to-water  heat  exchanger  and  the 
Cleaning  the  cooling  tower  or 
condenser  water  loop  with  harsh 
chemicals  such  as  hydrochloric  acid 
(muriatic  acid),  chlorine  or  other 
chlorides,  can  damage  the 
refrigerant-to-water  heat  exchanger. 
Care  should  be  taken  to  avoid 
allowing  chemicals  to  enter  the 
refrigerant-to-water  heat  exchanger. 
See  Appendix A  - Heat Exchanger 
Corrosion  Resistance  for  more 
information. 
   CAUTION  
WATER FREEZING 
Failure  of  the  condenser  due  to 
freezing will allow water to enter the 
refrigerant  circuit  and  will  cause 
extensive  damage  to  the  refrigerant 
circuit components. Any damage to 
the equipment as  a result of water 
freezing in the condenser is excluded 
from  coverage  under  AAON 
warranties  and  the  heat  exchanger 
manufacturer warranties. 
   WARNING 










